Program code number (pro.code) 11 – Red Lion LEGEND User Manual
Page 13
PROGRAM CODE NUMBER (PRO.CODE)
In two of the Program Disable states, it is necessary to enter the
PRO.CODE number before gaining access to the programming menus. The
default value for the code is “00”, but should be programmed differently. This
helps prevent inadvertent entry into the unit programming menus (See
Program Options Module). The PRO.CODE prompt is viewed when
PROGRAM MODE is displayed and the enter key is pressed. At this time, the
Code Number must be entered using the arrow keys. If the wrong code
number is entered, the operator will NOT be able to enter the programming
loop and the unit returns to the main display loop.
FRONT PANEL ACCESSIBLE FUNCTIONS WITH PROGRAM
DISABLE
The Legend Plus has several ways to limit the programming of parameters
from the front panel keypad. The Operator Access section of the Program
Options Module is used with the Program Disable (PGM.DIS.) DIP switch
and a User Input selected for PGM.DIS to limit programming. To enter the
programming loop, a code number may need to be entered, depending on the
Program Disable setting. Only an external User Input can be selected for
Program Disable. The following list describes the possible program disabling
settings.
PGM.DIS.
SWITCH
USER INPUT
TERMINAL
PROGRAM
CODE
NUMBER
ACTION
OFF
INACTIVE or Not
Programmed for
PGM.DIS
ALL
All programming enabled.
OFF
ACTIVE
0 to 98
Operator Accessible Functions
Enabled, Programming Loop
Accessible via code number.
OFF
ACTIVE
99
Operator Accessible Functions
Enabled, Programming Loop
Disabled.
ON
INACTIVE or Not
Programmed for
PGM.DIS
0 to 98
Operator Accessible Functions
Enabled, Programming Loop
Accessible via Code number.
ON
INACTIVE or Not
Programmed for
PGM.DIS
99
Operator Accessible Functions
Enabled, Programming Loop
Disabled.
ON
ACTIVE
ALL
Operator Accessible Functions
Disabled, Programming Loop
Disabled.
Note: If the User Input, set for PGM.DIS., is changed to another function, make
sure the User Input is not low (active). If the input is low when the function is
changed, the program disable function will remain active.