TROUBLESHOOTING GUIDE (Cont’d)
PROBLEMS
POSSIBLE CAUSE
REMEDIES
COUNT, PEAK, OR VALLEY VALUES
WILL NOT RESET WHEN A MANUAL
RESET IS PERFORMED
1. User input NOT properly programmed.
1 . V e r i f y p r o g r a mmi n g i n “ P r o g r a m U s e r
Module”.
CAN NOT ENTER INTO
PROGRAMMING MENUS
1. Front panel disabled.
1. Check “Front Panel Accessible Functions
With Program Disable” section in manual.
PRESETS, COUNTER LOAD, OR
SCALE FACTORS CAN BE VIEWED
BUT NOT CHANGED
1. Front panel disabled.
1. Verify programming in “Program Options
Module” sub menu Operator Access.
2. Check “ Front Panel Accessible Functions
With Program Disable” section of manual.
UNIT COUNTS WHILE RESET IS
ACTIVATED
1. User input Reset mode set for Momentary reset.
1. Program User input to a Maintained reset.
OUTPUT WILL NOT RESET
1. Output assigned to wrong display (Count or Rate).
1. Verify programming in “Program Outputs
Module”.
2. Reset with count disabled (Program Outputs Module).
2. Verify programming in “Program Outputs
Module”.
3. User input NOT properly programmed.
3 . V e r i f y p r o g r a mmi n g i n “ P r o g r a m U s e r
Module”.
NO RATE INDICATION
1. No signal at input A.
1. Check sensor connections.
a. Verify power to sensor.
2. Type of input signal selected incorrectly.
2. Check DIP switch setting on side of unit.
3. Rate Scale factor and/or Rate Scale Multiplier too
small.
3. Check scale factor value and scale multiplier
values.