beautypg.com

Outputting reading once from all transmitters, Communicating with a transmitter in poll mode, Open – Vaisala MMT330 User Manual

Page 96: Close

background image

User's Guide _______________________________________________________________________

96 ___________________________________________________________________ M210764EN-F

Outputting Reading Once From All Transmitters

Use the DSEND command to output the reading once from all connected
transmitters that are in STOP or POLL modes. In order to avoid data
collisions, the transmitters will send their response after a suitable delay.
The response includes the transmitters’s address, followed by their
measurement message.

NOTE

The total execution time of the DSEND command depends on the bit rate
of the serial port connection. At slow speeds, it will take a considerable
amount of time for devices with large address number to respond. The
delay will be the same even if there are no other devices at all.


DSEND

Example (transmitters with addresses 3 and 25 responding):

>dsend
3 aw= 0.261 T= 23.8 'C
25 aw= 0.277 T= 23.5 'C
>

Communicating with a Transmitter in POLL
Mode

OPEN

When all transmitters on the RS-485 bus are in POLL mode the OPEN
command sets one transmitter temporarily to STOP mode so that other
commands can be entered.

OPEN [aa]

where

aa =

Address of the transmitter (0 ... 99)

CLOSE

The CLOSE command switches the transmitter back to the POLL mode.

Example:

>open 2

(opens the line to transmitter 2, other

transmitters stay in POLL mode)

>?

(for example, display device information)

...
>close

(line closed)