Measurement Data (Read-Only)

Table 35

Measurement Data Registers

Name

Float

Integer

Unit

T

0003…0004

0258 (×0.01)

°C

a

w

0029…0030

0271 (×0.0001)

Available measurements depend on the instrument configuration. Values
may be unavailable also in case of device failure. Read status registers or
exception status outputs to check for failures.

NOTE

Only real-time data can be read from the instrument. Data that is
recorded in the transmitter’s memory (internal memory or data logger
module) cannot be read through Modbus.

Status Registers (Read-Only)

Table 36

Status Registers

Name

Address

Description

Fault status

0513

1 = No errors

Online status

0514

1 = Online data available

Error code (bits 15…0)

0516

Bit field that represents the
error codes listed in Table 29
on page 138. Active errors are
set to 1. For example, if bit 14
is set to 1, error code E14 is
active.

Error code (bits 31…16)

0517


Error information can retrieved also with function code 08, sub-function
02.

NOTE

Basic status information of the MMT330 transmitter is also available
with the Read Exception Status function code 07. For details, see section
Exception Status Outputs on page 167.