Clear
Press the Clear button to clear the alarms for this output only. This func-
tion clears both the dialog box entries and the settings in the data logger.
You must press this button for each of the individual outputs you want to
clear.
Contact Specifications
The “contact” closure is provided by a photo-coupled MOS device.
Because it is a solid-state device, it is not subject to arcing and contact-
welding as are mechanical relays. However, since it is a solid-state
device, it will be damaged by operation beyond its ratings, which are:
Nominal Load Voltage: . . . . . . . 28 V AC or 48 V DC, Maximum
Peak Voltage: . . . . . . . . . . . . . . ± 60 V, Maximum
Load Current: . . . . . . . . . . . . . . ± 1.8 A, continuous Maximum at 77°F (25°C),
. . . . . . . . . . . . . . . . . . . . . . . . . derated to 0.7 A at 185°F (85°C)
ON Resistance: . . . . . . . . . . . . . 0.12 Ohm, Maximum
Note:
Upon power up (powering the console or Envoy), the data logger will briefly test all four outputs
by closing the circuit (turning on the output). It is recommended that you disconnect any equip-
ment attached to the data logger outputs before rebooting the console or Envoy.