Vision calibration, Hand assembly testing, Audit – HP NonStop G-Series User Manual

Page 66: Audit definitions

background image

Configuring and Testing the Tape Library

L700 (CTL700) Installation and User’s Guide 527338-008

5- 12

Vision Calibration

Theta motor calibration. The theta mechanism moves from theta-stop to theta-stop.
The distance and time for this motion is compared against the mechanism
parameters within the firmware. There are three capacity variations for the tape
library (1/3, 2/3, and full), and the tape library size is also determined during this
step.

Vision Calibration

After calibration of the robotic motors, the robot moves to the vision calibration decal
(below Drive Column 0 at Panel 0). Thresholds for the line scan camera are:

Target is the readability and accuracy of the target image for locating array
positions.

Bar Code is the readability and accuracy of bar code information.

During normal operation, the camera is turned off, and tape cartridges are located by
referencing the VOLSET and cell location within the MPC card memory.

Hand Assembly Testing

Calibration and testing of the hand assembly is accomplished near the vision
calibration decal. The proximity sensor is aimed at the decal and tested to be on. The
hand is then moved away from the decal, and the sensor is tested to be off.

The gripper mechanism is extended to test for proper opening and closing.

Audit

The next step for initialization is the audit of the tape library. The audit process requires
five minutes.

Audit Definitions

An audit is the process of checking each cell within a tape library. If a cell contains a
tape cartridge, the camera reads the VOLSER and transfer this data to the MPC card.
The MPC card calculates the robotic position of the hand assembly (by referencing the
theta and Z positions) and catalogs the tape cartridge location by:

VOLSER

SCSI element number or panel, row, column

If a customer cell is empty, the location is recorded as “cell empty.” The reserved cells
(explained later in this section) are checked for cleaning cartridges (which
automatically configure the auto clean option) and for diagnostic test cartridges.

Note. The camera is operational during initialization, during audit, and when tape cartridges
are entered into a CAP.