Specifications and Dimensions

F8138601

34

The washer-extractor should be connected to an

individual branch circuit not shared with lighting or

other equipment.
The connection should be shielded in a liquid-tight or

approved flexible conduit with proper conductors of

correct size installed in accordance with the National

Electric Code or other applicable codes. The

connection must be made by a qualified electrician

using the wiring diagram provided with the washer-

extractor, or according to accepted European standards

for equipment labeled with the CE mark.
Refer to serial plate for recommended circuit breaker

size and determine wire size based on local code

requirements.
Refer to serial plate for recommended wire sizes for

runs up to 50 feet (15.24 meters). Use next larger size

for runs of 50 to 100 feet (15.24 to 30.48 meters). Use

2 sizes larger for runs greater than 100 feet (30.48

meters).
For personal safety and for proper operation, the

washer-extractor must be grounded in accordance with

state and local codes. If such codes are not available,

grounding must conform with the National Electric

Code, article 250 (current edition) or accepted

European standards for equipment labeled with the CE

mark. The ground connection must be made to a

proven earth ground, not to conduit or water pipes.

Refer to Figure 21 and 22.

Figure 21

Figure 22

Machines can be converted for lower voltage

operation and/or 50 Hz operation. Refer to conversion

label by serial plate for details.
After electrical installation is complete, run the

machine through a test cycle and check for a clockwise

basket rotation during the extract step. If rotation is not

clockwise, disconnect the power from the machine and

have a qualified electrician reverse any 2 motor leads.

Do not use a phase adder on any variable-

speed machine.

SW037

CAUTION

Electrically heated machines DO NOT

require dual power sources. Do not

connect customer power or customer load

to the Internal Load Distribution terminal

block. Refer to the machine electrical

schematic for details.

W759

WARNING

PHM700N

1

Grounding Lug: Connect to proven earth
ground

2

Customer Input Power Terminals

3

Internal Load Distribution - DO NOT connect
customer power source or load.

PHM721N

1

Grounding Lug: Connect to proven earth
ground

2

Customer Input Power Terminals

L1

L2

L3

SERVICE

GROUND

CHASIS

TB1

PHM

2

1

3

MACHINES WITH ELECTRIC HEAT

L1

SERVICE

GROUND

CHASIS

TB1

L2

L3

P

1

2

MACHINES WITHOUT ELECTRIC HEAT