8. Maintenance and servicing information

Pos : 460 /Anleit ungen/El ektr oni k/FU und St art er/9. Wartungs- und Ser vic ehi nweise/9. 1 Wart ungs hinweis e @ 0\mod_1328189536205_388.doc x @ 14535 @ 25566 @ 1

8.1 Maintenance Instructions

In normal use, frequency inverters are maintenance free if used correctly. Please note the "General
data" in Chap. Fehler! Verweisquelle konnte nicht gefunden werden..

Dusty environments

If the frequency converter is used in a dusty environment, the cooling surfaces should be regularly
cleaned with compressed air. If air intake filters have been built into the control cabinet, then these
should also be regularly cleaned or replaced.

Long-term storage

The frequency inverter must be regularly connected to the supply network for at least 60 min.

If this is not carried out, there is a danger that the frequency inverter may be destroyed.

If a device is to be stored for longer than one year, it must be re-commissioned with the aid of an
adjustable transformer before normal connection to the mains.

Long-term storage for 1 - 3 years

30 min with 25% mains voltage

30 min with 50% mains voltage

30 min with 75% mains voltage

30 min. with 100% mains voltage

Long-term storage for >3 years or if the storage period is not known:

120 min with 25% mains voltage

120 min with 50% mains voltage

120 min with 75% mains voltage

120 min. with 100% mains voltage

The device must not be subject to load during the regeneration process.

After the regeneration process, the regulations described above apply again (at least 60 min on the
mains 1x per year).

NOTICE

24 V control voltage

The 24 V control voltage supply must also be connected for SK 5x5E devices up to size 4.

Pos : 461 /Anleit ungen/El ektr oni k/FU und St art er/9. Wartungs- und Ser vic ehi nweise/9. 2 R epar at urhi nweis e @ 0\ mod_1328189697671_388. doc x @ 14558 @ 233 @ 1

8.2 Repair information

If you contact our technical support, please have the precise device type (rating plate/display),
accessories and/or options, the software version used (P707) and the series number (name plate) at
hand.