SK 500E – Brief instructions for frequency inverters

52

BU 0540 GB-1013

E003

3.0

Overcurrent, I

2

t limit

Inverter: I

2

t limit has triggered, e.g. > 1.5 x I

n

for 60s (please

also note P504)

Continuous overload at FI output

3.1

Overcurrent, chopper I

2

t

Brake chopper: I

2

t limit has triggered, 1.5x value attained for

60s (also note P554, if present, as well as P555, P556,
P557)

Avoid overload of brake resistance

3.2

Overcurrent IGBT

Monitoring 125%

De-rating (power reduction)

125% overcurrent for 50ms

brake chopper current too high

for fan drives: enable flying start circuit (P520)

3.3

Overcurrent IGBT

Monitoring 150%

De-rating (power reduction)

150% overcurrent

brake chopper current too high

Pos : 401 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E004 [ SK 180E/ SK 2xxE/Fehler E004 [SK 180E/SK 2xxE/ SK 5xxE] @ 2\ mod_1347453306910_388. doc x @ 46501 @ @ 1

E004

4.0

Overcurrent, module

Error signal from module (short duration)

Short circuit or earthing at FI output

Motor cable is too long

Use external output choke

Brake resistor defective or resistance too low

The occurrence of the error can greatly reduce the
service life of the FI and even cause its destruction.

4.1

Overcurrent measurement

"Overcurrent measurement"

P537 (pulse current switch-off) was reached 3x within 50ms
(only possible if P112 and P536 are disabled)

FI is overloaded

Drive sluggish, under-dimensioned,

Ramps (P102/P103) too steep -> Increase ramp time

Check motor data (P201 … P209)

Pos : 402 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E005 [ SK 180E/ SK 2xxE/Fehler E005 [SK 180E/SK 2xxE/ SK 5xxE] @ 2\ mod_1347453309234_388. doc x @ 46526 @ @ 1

E005

5.0

Overvoltage UZW

Inverter link voltage is too high

Extend deceleration time (P103)

If necessary, set switch-off mode (P108) with delay
(not for lifting equipment)

Extend emergency stop time (P426)

FIs with brake chopper:

Reduce energy return by means of a braking
resistance

Check the function of the connected brake resistor
(broken cable?)

The resistance of the connected brake resistor is too
high

5.1

Mains overvoltage

Mains voltage is too high

See technical data

Pos : 403 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E006 [ SK 5xxE] @ 2\ mod_1361458416246_388. doc x @ 58807 @ @ 1

E006

6.0

Charging error

Link circuit voltage is too low

Mains voltage too low

See technical data

6.1

Mains undervoltage

Mains voltage too low

See technical data

Pos : 404 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E007 [ SK 5xxE] @ 2\ mod_1361460003356_388. doc x @ 58882 @ @ 1