2 Assembly and installation

BU 0540 GB-1013

21

NOTICE

Total currents

5V / 15V (24V) can be obtained from several terminals if required. With size 1 ... 4, the total output current must
not exceed 250mA/150mA (5V/15V). Above Size 5 the limiting value is 250mA/200mA (5V/24V).

Pos : 56 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- Klemmenbl oc k X3 - R elais [SK 500. .. 535E] @ 1\ mod_1341401431286_388.doc x @ 29221 @ 5 @ 1

Terminal block X3, (above size 8: X3.1 and X3.2) - Relay

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

Terminals X3:

1

2

3

4

K1.1

K1.2

K2.1

K2.2

Name

Terminal Function

[Factory setting]

Data

Description / wiring suggestion

Parameter

1

2

Output 1

[Braking control]

Relay closing contact

230 VAC, 24 VDC,

< 60 VAC in circuits with
safe isolation,
≤ 2 A

Brake control

(closes on enabling)

P434

3

4

Output 2

[Ready/Fault]

Fault / Ready

(closes when FI ready / no fault)

P441