beautypg.com

NORD Drivesystems BU0540 User Manual

Page 40

background image

SK 500E – Brief instructions for frequency inverters

40

BU 0540 GB-1013

Parameter
No. [Array]

Name

Factory

setting

Super-

visor

Setting after commissioning

P 1

P 2

P 3

P 4

P211

(P) Dynamic boost [%]

100

S

P212

(P) Slip compensation [%]

100

S

P213

(P) Adjustment of ISD control [%] 100

S

P214

(P) Torque precontrol [%]

0

S

P215

(P) Boost precontrol [%]

0

S

P216

(P) Time boost precontrol [s]

0.0

S

P217

(P) Oscillation damping [%]

10

S

P218

(P) Modulation depth [%]

100

S

P219

Auto. flux optimisation [%]

100

S

P220

(P) Parameter identification

0

*) dependent on FI power or P200/P220

CONTROL PARAMETER Encoder input, only SK 520E/53xE

P300

(P) Servo Mode [On / Off]

0

P301

Incremental encoder

6

P310

(P) Speed controller P [%]

100

P311

(P) Speed controller I [%/ms]

20

P312

(P)

Torque current controller P [%]

200

S

P313

(P)

Torque current controller I [%/ms]

125

S

P314

(P) Motor current control limit [V]

400

S

P315

(P) Field current controller P [%]

200

S

P316

(P)

Field current controller I [%/ms]

125

S

P317

(P)

Limit, field current controller [V]

400

S

P318

(P)

Field weakening controller P [%]

150

S

P319

(P)

Field weakening controller I
[%/ms]

20

S

P320

(P) Field weakening limit [%]

100

S

P321

(P)

Speed control I ventilation time

0

S

P325

Function encoder

0

P326

Encoder conversion

1.00

P327

Speed slip error [rpm]

0 (off)

P328

Speed slip delay [rpm]

0 (off)

CONTROL TERMINALS

P400

(P) Function analog input 1

1

P401

Mode analog in. 1

0

S

P402

Adjustment 1: 0% [V]

0.0

S

P403

Adjustment 1: 100% [V]

10.0

S

P404

Analog input filter 1 [ms]

100

S

P405

(P) Function analog input 2

0

P406

Analog input mode 2

0

S