beautypg.com

Adaptation above size 8, 3 electrical connections, power unit, Electrical connections, power unit – NORD Drivesystems BU0540 User Manual

Page 18

background image

SK 500E – Brief instructions for frequency inverters

18

BU 0540 GB-1013

Adaptation above size 8

The adaptation to the IT network is carried out via the DIP
switch "EMC Filter" (1). As delivered, this switch is in the "ON"
position.

For operation in an IT network the switch must be set to the
"OFF" position. The leakage current is reduced, with a
deterioration in the EMC compatibility.

Pos : 51 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 4 Elektrischer Ansc hluss Leis tungst eil [ BU 0500] @ 0\ mod_1325863684752_388.doc x @ 6078 @ 3 @ 1

2.2.3 Electrical connections, power unit

Before connecting the frequency inverter, the following must be observed:

1. Ensure that the mains supply provides the correct voltage and is suitable for the current required.

2. Ensure that suitable circuit breakers with the specified nominal current range are installed between

the voltage source and the inverter.

3. Connect the mains voltage directly to the mains terminals L1-L2/N-L3-PE (for each device)

4. A four-core cable must be used to connect the motor. The cable is connected to the motor

terminals PE-U-V-W.

5. If screened motor cables (recommended) are used, the cable screening must also be connected to

a large area of the metallic screening angle of the EMC Kit, however, at least to the electrically
conducting mounting surface of the control cabinet.

6. Above size 8, the cable lugs which are included in the scope of delivery must be used. After

crimping, these must be insulated with shrink hose.

Note

The use of shielded cables is essential in order to maintain the specified radio interference suppression level.

If certain wire end sleeves are used, the maximum cross-section which can be connected can be reduced.

To connect the power unit, the following tools must be used:

Frequency inverter

Tools

Type

Size 1 - 4

Screwdriver

SL / PZ1; SL / PH1

Size 5 - 7

Screwdriver

SL / PZ2; SL / PH2

Size 8 - 9

Socket wrench

SW 13

Table 4: Tools