NORD Drivesystems BU0540 User Manual
Page 26
SK 500E – Brief instructions for frequency inverters
26
BU 0540 GB-1013
Relevance
SK 500E
SK 505E
SK 510E
SK 511E
SK 515E
SK 520E
SK 530E
SK 535E
√
Terminals X7:
73
74
26
27
5
7
44*
40
* Terminal 44:
up to Size 4: VI
Size 5 and
above: VO
RS485
+
RS485 -
DIN6
DIN7
DOUT1
DOUT2
V…24V
GND/0V
Name
Terminal Function
[factory setting]
Data
Description / wiring suggestion
Parameter
73
Data cable RS485
Baud rate
9600…38400Baud
Termination resistance
R=120
W
BUS connection parallel to RS485 on
RJ12 plug
NOTE: The termination resistance of
DIP switch 1 (see RJ12/RJ45) can also
be used for terminal 73/74.
P503
P509
74
26
Digital input 6
[no function]
7.5...30V, R
i
=3.3k
W
As described for terminal block X5, DIN1
to DIN5.
Not suitable for the evaluation of a motor
thermistor.
P425
27
Digital input 7
[no function]
P470
5
Output 3 (DOUT1)
[no function]
Digital output
S1 to S4
18-30V, according to VI
24V, max. 20mA
size 5 and above
DOUT1 and DOUT2:
24V, max. 200mA
For inductive loads:
provide protection with a
free-wheeling diode.
For evaluation in a control system. The
scope of functions corresponds to that of
the relay (P434).
P450
7
Output 4 (DOUT2)
[no function]
P455
44
Size 1 to Size 4
VI 24V supply
voltage input
18…30V
at least 800mA (input)
Voltage supply for the FI control unit. Is
essential for the function of the
frequency inverter.
Size 5 and above
VO 24V supply
voltage output
24V ± 25%
max. 200mA (output)
Supply voltage provided by the
frequency inverter for connection to the
digital inputs or the supply of a 10-30V
encoder.
The 24V control voltage is generated by
the FI, however it can also be supplied
via the terminals X12:44/40. Supply via
terminal X7:44 is not possible.
40
Reference potential
for digital signals
0V digital
Pos : 68 /Anl eitungen/ Elektroni k/FU und Start er/ 2. M ont age und Ins tall ati on/ 2. 10. 5 Elektrischer Ansc hluss St euert eil- St ec kerbl oc k X9 und X10 – C AN / CAN open [SK 500. .. 535E] @ 1\ mod_1341402404239_388.doc x @ 29385 @ 5 @ 1