background image

4 Commissioning

BU 0540 GB-1013

35

4. Commissioning

Once the power supply has been connected to the frequency inverter, it will be operational within a
few moments. In this state, the frequency inverter can be set to the requirements of the application,
i.e. it can be configured. A completely comprehensive description of all the parameters is set out in
Section 0.

The connected motor may only be started after the parameters specific to the application in question
have been set by qualified personnel.

DANGER

Danger to life!

The frequency inverter is not equipped with a line main switch and is therefore always live when connected to the
power supply. Live voltages may therefore be connected to a connected motor at standstill.

Pos : 91 /Anl eitungen/ 4. Inbetriebnahme [ BU 0500]/ 4. 1 Werksei nst ellungen @ 0\ mod_1327569750609_388.doc x @ 7196 @ 2 @ 1

4.1 Factory settings

All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting
for standard applications with 4 pole IE1 three-phase motors (same voltage and power). For use with
motors with other powers or number of poles, the data from the rating plate of the motor must be input
into the parameters P201...P207 under the menu item >Motor data<.

NOTE:

All data for IE1 motors can be pre-set with parameter P200. After use of this
function has been successful, this parameter is reset to 0 = no change! The data is
loaded automatically into parameters P201...P209 – and can be compared again
with the data on the motor rating plate.

3~ Mot
IEC 56
IM B3

cos 0.74

cosj 0.74


IP55

Rot. KL 16

Th.Cl.F

EN60034

60 Hz

460 V Y

5.2 A

2.5 kW

1765 /min

1440 /min

P206

P201

P204

P203 P202

P200

9.0 / 5.2 A

50 Hz

2.2 kW

P207

P200 Motor list:
0 = no change

8 = 0.37kW 400V

1 = no motor

9 = 0.50PS 460V

2 = 0.25kW 230V

10 = 0.55kW 230V

3 = 0.33PS 230V

11 = 0.75PS 230V

4 = 0.25kW 400V

12 = 0.55kW 400V

5 = 0.33PS 460V

13 = 0.75PS 460V

6 = 0.37kW 230V

14 = 0.75kW 230V

7 = 0.50PS 230V ....

230 / 400 V D/Y

Fig. 3 Motor type plate