6 operating status messages – NORD Drivesystems BU0540 User Manual
Page 57
6 Operating status messages
BU 0540 GB-1013
57
C008
8.0
Parameter loss
Warning:
One of the cyclically saved messages such
as
operating hours or
enabling time could not be
saved successfully.
The warning disappears as soon as saving can be
successfully performed.
Pos : 427 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/ Warnung C 012 [SK 5xxE] @ 2\ mod_1361539953134_388. doc x @ 59296 @ @ 1
C012
12.1
Motor limit
"Motor switch-off limit"
Warning: 80 % of the drive torque switch-off limit (P534 [-
01]) has been exceeded.
• Reduce load on motor
• Set higher value in (P534 [-01]).
12.2
Generator limit
"Generator switch-off limit"
Warning: 80 % of the generator switch-off limit (P534 [-02])
has been exceeded.
• Reduce load on motor
• Set higher value in (P534 [-02]).
12.5
Load limit
Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
• Adjust load.
• Change limit values ((P525) ... (P527)).
• Increase delay time (P528).
Pos : 429 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ 6./ 6. /7.2 - Mel dungen Eins chalts perr e (Tabellenüberschrif t) @ 3\ mod_1361803467385_388. doc x @ 59922 @ 5 @ 1