beautypg.com

6 operating status messages – NORD Drivesystems BU0540 User Manual

Page 55

background image

6 Operating status messages

BU 0540 GB-1013

55

13.5

Reserved

Error message for POSICON

à see supplementary

instructions

13.6

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 412 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E014 "res er viert" [ SK 180E ... SK 5xxE] @ 2\ mod_1347454273854_388.doc x @ 46776 @ @ 1

E014

---

Reserved

Error message for POSICON

à see supplementary

instructions

Pos : 413 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E015 [ SK 180E ... SK 5xxE] @ 2\ mod_1347454278051_388.doc x @ 46801 @ @ 1

E015

---

Reserved

Pos : 414 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E016 [ SK 135E ... SK 5xxE] @ 2\ mod_1347454280625_388.doc x @ 46826 @ @ 1

E016

16.0

Motor phase error

A motor phase is not connected.

Check P539

Check motor connection

16.1

Magnetisation current
monitoring

"Magnetisation current
monitoring"

Required exciting current not achieved at moment of switch-
on.

Check P539

• Check motor connection

Pos : 415 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E018 "res er viert" [ SK 2xxE/F ehler E018 "reser vi ert" [ SK 2xxE/SK 5xxE] @ 2\ mod_1347454282777_388.doc x @ 46851 @ @ 1

E018

18.0

Reserved

Error message for "Safe Pulse Block"

à see supplementary

instructions

Pos : 416 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E019 [ SK 180E/ SK 2xxE/Fehler E019 [SK 180E/SK 2xxE/ SK 5xxE] @ 2\ mod_1347454285788_388. doc x @ 46876 @ @ 1

E019

19.0

Parameter identification

"Parameter identification"

Automatic identification of the connected motor was
unsuccessful

• Check motor connection

Check pre-set motor data (P201 ... P209)

19.1

Star / Delta circuit incorrect

"Star / delta motor circuit
incorrect

Pos : 417 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E020 /F ehl er E020 / E021 [ SK 135E .. . SK 5xxE] @ 2\ mod_1347454288768_388. doc x @ 46901 @ @ 1

E020

E021

20.0

Reserved

System error in program execution, triggered by EMC
interference.

Observe wiring guidelines

Use additional external mains filter.

Earth the FI very well.

20.1

Watchdog

20.2

Stack Overflow

20.3

Stack underflow

20.4

Undefined Opcode

20.5

Protected Instruct.

„Protected Instruction“

20.6

Illegal Word Access

20.7

Illegal Inst.

Access

“Illegal Instruction Access”

20.8

Program Memory Error

"Program memory error"
(
EEPROM error)

20.9

Memory Protection Error

21.0

NMI Error

(not used by hardware)

21.1

PLL Error

21.2

ADU Error "Overrun"

21.3

PMI Error "Access Error"

21.4

Userstack Overflow

Pos : 418 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E022 "res er viert" [ SK 5xxE] @ 2\ mod_1361527702934_388. doc x @ 59091 @ @ 1

E022

---

Reserved

Error message for PLC

à see supplementary instructions

Pos : 419 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ St örmel dungen/F ehl er E023 "res er viert" [ SK 5xxE] @ 2\ mod_1361527808170_388. doc x @ 59116 @ @ 1

E023

---

Reserved

Error message for PLC

à see supplementary instructions

Pos : 421 /Anleit ungen/6. / 7. Mel dungen z um Betriebsz ust and [BU 0500 / BU 0200]/ 6./ 7. 2 - Warnmeldungen (Tabellenüberschrif t) @ 3\ mod_1361803463080_388. doc x @ 59898 @ 5 @ 1