7 Technical data

BU 0540 GB-1013

59

7. Technical data

Pos : 436 /Anleit ungen/7. / 8. Technisc he Daten [BU 0500/ BU 0200] /SK 5xxE/ 7. 1 Allgemeine D at en SK 500E @ 0\ mod_1328183162552_388.doc x @ 13983 @ 2 @ 1

7.1 General Data SK 500E

Function

Specification

Output frequency

0.0 ... 400.0Hz

Pulse frequency

3.0 ... 16.0kHz, standard setting = 6kHz (from size 8 and above = 4kHz)
Power reduction > 8kHz for 230V devices, >6kHz for 400V devices.

Typical overload capacity

150% for 60s, 200% for 3.5s

Efficiency of frequency inverter

approx. 95% according to size

Insulation resistance

> 5MΩ

Ambient temperature

0°C ... +40°C (S1-100% ED), 0°C ... +50°C (S3-70% ED 10min)

Storage and transport temperature

-20°C ... +60 /70°C

Long-term storage

See BU 0500

Protection class

IP20

Max. installation altitude above sea
level

- up to 1000m: no reduction in power
- 1000...4000m: 1%/ 100m power reduction
*Up to 2000m: Overvoltage category 3
* up to 4,000m: Overvoltage category 2, mains input: Overvoltage protection
required

Ambient conditions

Transport (IEC 60721-3-2):

Vibration: 2M1

Operation (IEC 60721-3-3):

Vibration: 3M4;

climate: 3K3;

Waiting period between 2 x "Mains on" 60 sec for all devices in normal operating cycle

Protective measures against

Overtemperature of the frequency inverter,
overvoltage and undervoltage

Short-circuit, earthing fault,
overload

Regulation and control

Sensorless current vector control (ISD), linear V/f characteristic

Motor temperature monitoring

I

2

t-Motor (UL approval), PTC / Bi-metal switch (no UL approval)

Interfaces (integrated)

RS 485 (USS)
RS 232 (single slave)

CANbus (except SK 50xE)
CANopen (except SK 50xE)
Modbus RTU (SK 540E and
above)

Electrical isolation

Control terminals (digital and analog inputs)

Connection terminals

For details of tightening torques for the terminals: see Section 2.2.3 and 2.2.4.

External supply voltage,
control unit SK 5x5E

Size 1-4: 18…30V DC, at least 800mA
Size 5-7: 24…30V DC, at least 1000mA
size 8-9: 24…30V DC, at least 3000mA

Analog setpoint input / PID input

2x (size 5 and above: - 10V…) 0...10V, 0/4...20mA, scalable, digital 7.5...30V

Analog setpoint resolution

10 bit based on measurement range

Setpoint consistency

analog < 1% digital < 0.02%

Digital input

5x (2.5V) 7.5...30V, R

i

= (2.2k

W) 6.1kW, cycle time = 1...2ms

Additionally for SK 520E and above: 2x 7.5...30V, R

i

= 6.1k

W, cycle time =

1...2ms

Control outputs

2x relay 28V DC / 230V AC, 2A (output 1/2 - K1/K2)

Additionally, with SK 520E/530E: 2x DOUT 15V, 20mA or
Additionally, with SK 535E/545E: 2x DOUT 18…30V (depending on VI), 20mA, or

2x DOUT 18…30V, 200mA Size 5 and above

(Output 3/4 - DOUT1/2)

Analog output

0 ... 10V scalable