Resolution: 1 degree or 0.1 degree, selectable.

Line Voltage Stability: ±0.05% over the supply voltage range.

Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F)

maximum (100 ppm / °C typical, 200 ppm / °C maximum).

Common Mode Rejection: 140 db minimum at 60 Hz.

Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.

Isolation:

Relay and SSR outputs: 1500 VAC to all other inputs and outputs.

SP1 and SP2 Current outputs: 500 VAC to all other inputs and

outputs, but not isolated from each other,

SP1 and SP2 Switched Voltage outputs: 500 VAC to all other inputs

and outputs, but not isolated from each other.

24 VDC Loop Power: 500 VAC to all inputs and outputs.

Process Output: 500 VAC to all other inputs and outputs.

Supply Voltage: 100 to 240 VAC, nominal., +10 -15%, 50 to 400 Hz. single

phase; 132 to 240 VDC, nominal., +10 -20%.

Power Consumption: 5VA maximum.

Operating Temperature: -10 to +55 °C (+14 to 131 °F).

Storage Temperature: -40 to +80 °C (-40 to 176 °F).

Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at

55 °C non-condensing.

Memory Backup: Nonvolatile memory. No batteries required.
Control Output Ratings:

SSR: 2.5 A @ 240 VAC at 25 °C (77°F). Derates to 1.25 A @ 55° C
(130°F).
Relay: SPDT, 10 A @ 240 VAC resistive; 1/4 hp @ 120 VAC, 1/3 hp

@ 240 VAC.

Alarm Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC
inductive; Pilot Duty Rating: 240 VA, 2 A @ 125 VAC or 1 A @ 240
VAC.
Current (isolated): 0 to 20 mA across 600 ohms maximum.
Switched Voltage (isolated): 15 VDC @ 20 mA.

Loop Power Supply (isolated): 24VDC @ 50mA, regulated.
Panel Cutout: 92 mm x 45 mm (3.625" x 1.775").
Depth Behind Mounting Surface: 103 mm (4.0").
Weight: 369 g (13 oz).
Agency Approvals: CE, UL E87325
Front Panel Rating: Type 4X, (IP66).