Alarm 2 Inhibit: Select On or OFF.
On
Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF
Alarm Inhibit is OFF.
A2St
Alarm 2 Output State: Select CLOS or OPEn.
CLOS
Closes Contacts at Alarm Set Point.
OPEn
Opens Contacts at Alarm Set Point.
A2LP
Alarm 2 Lamp: Select O on or OoFF.
O on
Alarm Lamp is ON when alarm contact is closed.
OoFF
Alarm Lamp is OFF when alarm contact is closed.
A2Lb
Alarm 2 Loop Break. Select On or OFF.
On
Loop Break Condition will cause an Alarm Condition.
OFF
Loop Break will not affect the Alarm Condition.
SPSA
(Option 948, 4-Stage Set Point) Switch Action: Select rE or Int.
rE
Set Point Stage selected by external contact closures.
Int
Set Point Stage selected by internal menu selection. See
SP menu item in Secondary Menu.
Addr
(Option 992, 993, Serial Communications) Control Address: Set
from 1 to 3FF. This number (hexadecimal, base 16) must match the
address number used by the host computer.
bAUd
(Option 992, 993, Serial Communications) Communication Baud
Rate: Select 300, 1200, 2400, 4800, 9600, or 19200. This number
must match the baud rate used by the host computer.
nAt
(Option 992, 993, Serial Communications) No Activity Timer: Set
from OFF or 1 to 99 minutes.
1 - 99
Maximum time between host computer accesses. If timer
counts to 0, CHEC/LorE will be displayed.
OFF
No Activity Timer function is disabled.
rSCL
(Option 924, 926, 928, Analog Remote Set Point) Remote Scale
Low: Select 100 to 9999 counts below rSCH. The total span between
rSCL and rSCH must be within 11998 counts. Maximum setting
range is -1999 to +9999 counts.
rSCH
(Option 924, 926, 928, Analog Remote Set Point) Remote Scale
High: Select 100 to 9999 counts above rSCL. The total span between
rSCL and rSCH must be within 11998 counts. Maximum setting
range is -1999 to +9999 counts.