Dwyer 8600 User Manual
Page 24

949-1277-3
Page 24
December, 1998
Prog
Ramp/Soak Feature: Select On or OFF
On
Allows Programmed Ramp/Soak function to be started
by the Run/Hold key on the control front panel.
OFF
Turns Ramp/Soak function OFF and resets program to
beginning.
PSEt
Programmer function set. Select On or OFF.
Off
Skip Ramp/Soak Programming. Go to next Secondary
Menu Item, InPC on the next page.
On
Enable Ramp/Soak Programming.
StAt
Programmer Status Display in the Primary Menu when Prog (above)
is On: Select On or OFF.
OFF
The Primary Menu operates as normal.
On
The Primary Menu is altered to have the following items
inserted before the SP1 menu item: ####/ti (time
remaining in segment), ####/##ti (total time in active
segment), and ####/##SP (segment target set point).
tbAS
Ramp/Soak Time Base. Select 1_S or 60_S.
1_S
Ramp/Soak time base is in 1 second increments. Pro-
gram time 1ti...16ti is measured in seconds.
60_S
Ramp/Soak time base is in 60 second increments (min-
utes). Program time 1ti...16ti is measured in minutes.
The following items repeat in the following order: 1ti, 1SP, 1A1 (if
alarm 1 is programmed as an event), 1A2 (if alarm 2 is programmed as
an event), 2ti, 2SP, 2A1, 2A2, . . . , 16ti, 16SP, 16A1, 16A2. To avoid
repetition each item will only be described once.
1ti
Segment Time: Select 0 to 9999 units (minutes if tbaS is set to
60_S, seconds if tbaS is set to 1_S.
1SP
Segment Set Point: Select value as desired.
1A1
Segment Alarm 1 Event: Select On or OFF .
On
Alarm 1 is active during segment 1 time (1ti).
OFF
Alarm 1 is inactive during segment 1 time (1ti).
1A2
Segment Alarm 2 Event: Select On or OFF.
On
Alarm 2 is active during segment 1 time (1ti).
OFF
Alarm 2 is inactive during segment time (1ti).