increase. Most commonly used in cooling processes.

rE

Reverse Action. As the input increases the output will
decrease. Most commonly used in heating processes.

If Out2 is set for ##tP, #PUL, or ProP,then S2OL and S2OH (following)
appear. If Out2 is set for ONOF, then skip to S2rE.

S2OL

Set Point Output Low Limit: Select 0 to 100% but not greater than
S2OH. This item limits the lowest output value. This is useful for
adding a bias to the process when needed. Factory set to 0 for
output codes 1,2, and 3. Factory set to 20 for output code 5 (20%
output equals 4 mA output).

S2OH

Set Point 1 Output High Limit: Select 0 to 100% but not less than
S2OL for output codes 1, 2, or 3. Select 0 to 102% but not less than
S2OL for output code 5. This item allows setting the maximum
output limit. This is useful with processes that are over powered.
Adjustment to 102% allows setting current output to force a full on
condition for output devices which do not have bias adjustments.
Factory set to 100 for all output codes.

S2rE

Set Point 2 Reset. Select OnOF or Hold.
OnOF

Control will automatically reset when process passes
back through SP2d.

HoLd

Manual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.

S2Pi

Set Point 2 Power Interrupt. Select On or OFF.
On

Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.

OFF

Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.

S2iH

Set Point 2 Inhibit: Select On or OFF.
On

Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.

OFF

Alarm Inhibit is OFF.

S2LP

Set Point 2 Lamp: Select O on or OoFF.
O on

Lamp ON when Output is ON.

OoFF

Lamp OFF when Output is ON.