Dwyer 8600 User Manual
Page 29

December, 1998
Page 29
949-1277-3
S1OH
Set Point 1 Output High Limit: Select 0 to 100% but not less than
S1OL for output codes 1, 2, or 3. Select 0 to 102% but not less than
S1OL for output code 5. This item allows setting the maximum
output limit. This is useful with processes that are over powered.
Adjustment to 102% allows setting current output to force a full on
condition for output devices which do not have bias adjustments.
Factory set to 100 for all output codes.
If Out1 is set for ##tP, #PUL, or ProP,then skip to S1LP below.
S1rE
Set Point 1 Reset. Select OnOF or Hold.
OnOF
Control will automatically reset when process passes
back through SP1d.
HoLd
Manual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.
S1Pi
Set Point 1 Power Interrupt. Select On or OFF.
On
Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.
OFF
Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.
S1iH
Set Point 1 Inhibit: Select On or OFF.
On
Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.
OFF
Alarm Inhibit is OFF.
S1LP
Set Point Lamp: Select O on or OoFF.
O on
Lamp ON when Output is ON.
OoFF
Lamp OFF when Output is ON.
If your control is not equipped with Set Point 2, then proceed to the
alarm section (next page).
S2t
Set Point 2 type: Select Abs or dE.
AbS
Absolute SP2. SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.
dE
Deviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is
changed (tracking SP2).
S2St
Set Point 2 State: Select dir or rE.
dir
Direct Action. As the input increases the output will