Set Point 1 Output High Limit: Select 0 to 100% but not less than
S1OL for output codes 1, 2, or 3. Select 0 to 102% but not less than
S1OL for output code 5. This item allows setting the maximum
output limit. This is useful with processes that are over powered.
Adjustment to 102% allows setting current output to force a full on
condition for output devices which do not have bias adjustments.
Factory set to 100 for all output codes.

If Out1 is set for ##tP, #PUL, or ProP,then skip to S1LP below.

S1rE

Set Point 1 Reset. Select OnOF or Hold.
OnOF

Control will automatically reset when process passes
back through SP1d.

HoLd

Manual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.

S1Pi

Set Point 1 Power Interrupt. Select On or OFF.
On

Alarm Power Interrupt is On. Control will automatically
reset on power-up if no alarm condition exists.

OFF

Alarm Power Interrupt is OFF. Control will power-up in
alarm condition regardless of condition of process.

S1iH

Set Point 1 Inhibit: Select On or OFF.
On

Alarm Inhibit is On. Alarm action is suspended until the
process value first enters a non-alarm condition.

OFF

Alarm Inhibit is OFF.

S1LP

Set Point Lamp: Select O on or OoFF.
O on

Lamp ON when Output is ON.

OoFF

Lamp OFF when Output is ON.

If your control is not equipped with Set Point 2, then proceed to the
alarm section (next page).

S2t

Set Point 2 type: Select Abs or dE.
AbS

Absolute SP2. SP2 is independent of SP1, and may be set
anywhere between the limits of SPL and SPH.

dE

Deviation SP2. SP2 is set as a deviation from SP1, and
allows SP2 to retain its relationship with SP1 when SP1 is
changed (tracking SP2).

S2St

Set Point 2 State: Select dir or rE.
dir

Direct Action. As the input increases the output will