Diagnostic error messages – Dwyer 8600 User Manual

Page 37

background image

December, 1998

Page 37

949-1277-3

SPECIFICATIONS

Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current

selectable.

Input Impedance:

Thermocouple = 3 megohms minimum.

RTD current = 200 µA.

Current = 10 ohms.

Voltage = 5000 ohms.

Sensor Break Protection: De-energizes control output to protect system

after customer set time. (See InPt in Secondary Menu.)

Set Point Range: Selectable (See Range Chart Page 39).

Display: Two 4 digit, 7 segment; vertical 7.62mm (0.3") high LEDs;

horizontal 10mm (0.4") high LEDs.

Control Action: Reverse (usually heating), Direct (usually cooling) select-

able.

Proportional Band: 1 to 9999 °F, °C, or counts.

Reset Time (Integral): Off or 0.1 to 99.9 minutes.

Rate Time (Derivative): Off or 0.01 to 99.99 minutes.

Cycle Rate: 1 to 80 seconds.
On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F,

1° C, or 1 count steps.

Alarm On - Off Differential: 1° F, 1° C, or 1 count.

Fuzzy Percent: 0 to 100%.

Fuzzy Rate: Off or 0.01 to 99.99 minutes.

Fuzzy Band: Off or 1 to 4000 °F, °C, or counts.

Accuracy: ±0.25% of span, ±1 least significant digit.

DIAGNOSTIC ERROR MESSAGES

DISPLAY

ArEA

(Alter-

nates

with PV)

ArEA

MEANING

This message ap-
pears if the ambient
temperature of the
control approaches
the ends of tol-
erence.

This message ap-
pears if the ambi-
ient temperature of
the control is out of
range or RJC sen-
sor is broken.

SP OUTPUTS

Set point

outputs active

Alarm active

Set point

outputs active

Alarms active

ACTION REQUIRED

Correct the ambient tempera-
ture conditions. Ventilate the
area of the cabinet or check
for clogged filters. If RJC bro-
ken, return to factory for ser-
vice.

Correct the ambient tempera-
ture conditions. Ventilate the
area of the cabinet or check
for clogged filters. If RJC bro-
ken, return to factory for ser-
vice.