CLOS

Closes Contacts at Alarm Set Point.

OPEn

Opens Contacts at Alarm Set Point.

A1LP

Alarm 1 Lamp: Select O on or OoFF.
O on

Alarm Lamp is ON when alarm contact is closed.

OoFF

Alarm Lamp is OFF when alarm contact is closed.

A1Lb

Alarm 1 Loop Break. Select On or OFF.

On

Loop Break Condition will cause an Alarm Condition.

OFF

Loop Break will not affect the Alarm Condition.

AL2

Alarm 2 function: Select OFF, Lo, Hi, HiLo, or Evnt.
OFF

Alarm 2 is disabled. No Alarm 2 menu items appear in
the Secondary or Secure menus.

Lo

Low Alarm Only. A2Lo appears in the Secondary Menu.

Hi

High Alarm Only. A2Hi appears in the Secondary Menu.

HiLo

High and Low Alarms. Both A2Lo and A2Hi appear in
the Secondary Menu, and share the same Alarm 2 Relay
output.

Evnt

Alarm 2 is controlled by the Ramp/Soak program func-
tion. See pages 10-13, and 20 (#A2) for further informa-
tion.

If AL2 is set to OFF, the Secure Menu ends. If AL2 is set to Evnt, go to A2St
below.

A2t

Alarm 2 Type: Select AbS or dE
AbS

Absolute Alarm that may be set anywhere within the
values of SCAL and SCAH and is independent of SP1.

dE

Deviation Alarm that may be set as an offset from SP1.
As SP1 is changed the Alarm Point will track with SP1.
A deviation alarm will also track any active ramp or soak
set point.

A2rE

Alarm 2 Reset: Select OnOF or Hold.
OnOF

Automatic Reset.

Hold

Manual Reset. Reset (acknowledge) by simultaneously
pressing the INDEX & DOWN ARROW keys for 5
seconds.

A2Pi

Alarm 2 Power Interrupt: Select On or OFF.
On

Alarm Power Interrupt is On.

OFF

Alarm Power Interrupt is OFF.