Badger Meter SRD/SRI Valve Positioners User Manual
Page 78

4-20 mA Intelligent without Communication
(replaces SRD992) and ATEX Certification
Electrical classification
1) 2)
(Electronics family AI 638 per EC- Certificate of
Conformity PTB 00 ATEX 2128)
see Certificates of Conformity EX EVE0105 A
Type of protection ATEX “intrinsic safety”
. . . . . . . . . . . . . . . . . II 2 G EEx ia IIB/IIC,
II 2 G EEx ib IIB/IIC
Temperature classes
Type AI 638 HI. . . . . . . T4, Model Code EA4
Certificate of Conformity . . . . PTB 00 ATEX 2128
For use in hazardous areas in circuits certified as intrinsic-
ally safe with the following maximum values:
Input circuit:
Ui = 30 V, Ii = 130 mA, Pi = 0.9 W
Li = 5 µH, Ci = 1.3 nF (5.3 nF to earth)
Ambient temperature range:
Temperature class T4: . . . . . .–40 °C to + 80 °C
Explosion protection Zone 2
It is recommended to use the positioner with explosion pro-
tection “intrinsically safe” (consider temperature class).
In the Federal Republic of Germany these positioners may
be operated in Zone 2 with non-intrinsically safe circuits if
the operating values do not exceed the maximum reference
values.
Type of protection FM “intrinsic safety”
(Electronics family per BIM 638 (GI, Rev 2.0))
Cl. I, Div 1, Gp ABCD; Cl. II, Div 1, Gp EFG; Cl. III, Div 1
hazardous locations indoor and outdoor, T6/T4,
NEMA Type 4X
Type of protection FM “non-incendive”
(Electronics family per BIM 638 (GI, Rev 2.0))
Cl. I, Div 2, Gp ABCD; Cl. II, Div 2, Gp FG; Cl. III, Div 2
hazardous locations indoor and outdoor, T6/T4,
NEMA Type 4X
Type of protection CSA “intrinsic safety”
(Electronics family per CSA xxx)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X
1)
With appropriate order only
2)
National requirements must be observed
System Configuration
Page 78
August 2014
POS-UM-00010-EN-03