Badger Meter SRD/SRI Valve Positioners User Manual
Page 54

Split Range
Split-Range, PV_Scale Splitting
Split Range is useful if an additional control range is demanded
which cannot be covered by one valve only A valve of smaller
nominal size can be applied overtaking the smallest quantities;
a parallel mounted valve of bigger nominal size takes on the
larger quantities
With conventional positioners, this function is realized through
serial connection of the instruments and allocation of individual
regulating ranges (see drawing) With SRD with analog setpoint
value (version HART or “without communication”), this can be
adjusted with menus 5 5 and 5 6
The other versions of the SRD receive the set value via digital
means; the input data signal cannot be split The function
can be realized either in the primary control system, in which
setpoint values are calculated for each valve, or via the variables
PV_SCALE With PV_Scale the digital input setpoint value can be
assigned to the valve span
Example: At low current, only the smaller valve positions; from
approx 40% the large valve is added