SRD991 with HART or without Communication

(With the other versions of the SRD, these menus cannot be selected.)

5.5 Split Range 0 %

-

1

-

1

-

LED1 and LED 3 lights up

LED: The value that was adjusted e.g. with a loop calibrator at the input of
the SRD, is entered with confirmation of keys UP+DOWN as 0 % value.
LCD: By pressing of keys UP or DOWN the value is adjusted and confirmed
with keys UP+DOWN.

5.6 Split Range 100 %

-

-

-

1

1

LED 3 and LED 4 lights up

LED: The value that was adjusted e.g. with an loop calibrator at the input of
the SRD, is entered with confirmation of keys UP+DOWN as 0 % value.
LCD: By pressing of keys UP or DOWN the value is adjusted and confirmed
with keys UP+DOWN.

The keys have Autorepeat: By pressing and holding of a key UP or DOWN, the value is counted
upward, after some time in larger steps.

Example: An input current of 10.4 mA has to correspond to a valve position
of 100 %.