Badger Meter M-Series M4000 User Manual
Page 24

24
4. In EMPTY PIPE 15, select Cal. empty pipe.
5. Select Cal[OFF] E=ON, press or select E once to
change OFF to ON. (NOTE: Make sure the Flow Detector
Pipe is Empty.)
NOTE: With the pipe empty the usage reading should
be between 3.00 and 3.30 Volts.
6. Select Exit WITH save. Press E once to save the setting
and return to EMPTY PIPE 15.
7. In EMPTY PIPE 15, select at Cal. full pipe. Then, press E.
8. Select Cal[OFF] E=ON, press or select E once to change
to OFF to ON. (NOTE: Make sure the Flow Detector pipe
is full of fl uid.)
NOTE: The full pipe voltage reading should be below
3.00 Volts.
9. Press + once to move cursor to Exit WITH save. Press E
once to save the setting and return to EMPTY PIPE 15.
10. In EMPTY PIPE 15, press + three times to place cursor
at Enable/Disable. Next, press E.
11. In EMPTY CONTROL 1G, press + twice to move cursor
to Det[OFF] E=ON. Press E once to switch OFF to ON.
12. Press + once to move cursor to Exit WITH save. Press E
once to save the setting and return to EMPTY PIPE 15.
Pulse Output
1. Press E once to move cursor to Main Menu.
2. In the MAIN MENU 00, press + three times to move the
crusor to Inputs/Outputs. Next, press E.
3. At IN/OUTPUTS 30 press + three times to place the
cursor at Digital Out. #1. Press E.
4. In DIG OUTPUT 1 33, press + once to move the cursor
to Pulses / unit. Press E.