beautypg.com

Alicat LC Series Liquid Flow Controller User Manual

Page 33

background image

33

Tareing via RS-232 / RS-485 (L-Series only):

Tareing (or zeroing) the flow meter provides it with a reference point for

zero flow. This is a very simple but important step in obtaining accurate

measurements. It is good practice to “zero” the flow meter each time it is

powered up.
If the flow reading varies significantly from zero after an initial tare, give the

unit a minute or so to warm up and re-zero it. If possible, it is helpful to zero

the unit near the expected operating pressure by positively blocking the flow

downstream of the flow meter prior to entering the Tare command. Zeroing the

unit while there is any flow will directly affect the accuracy by providing a false

zero point.
If in doubt about whether the flow is positively blocked, remove it from the line

and positively block both ports before entering the Tare command. If the unit

reads a significant negative value when removed from the line and blocked, it

is a good indication that it was given a false zero. It is better to zero the unit at

atmospheric pressure and a confirmed no flow conditions than to give it a false

zero under line pressure. To send a Tare command via RS-232 / RS-485, enter

the following strings:
In Polling Mode:

Address$$V (e.g. B$$V)

Sending a Set-point via RS-232 / RS-485: To send a set-point via RS-232 / RS-485,

“Serial” must be selected under the “Input” list in the control set up mode.
Method 1: Set-point may be set in floating point in serial communication using

serial command (UnitID)SX.YZ

Example: AS4.54 results in Unit ID A changing set-point to 4.54.

Method 2: Type in a number between 0 and 65535 (2% over range), where 64000

denotes full-scale flow rate, and hit “Enter”.
The set-point column and pressure rates should change accordingly. If they do

not, try hitting “Enter” a couple of times and repeating your command. The

formula for performing a linear interpolation is as follows:

Value = (Desired Set-point X 64000) / Full Scale Flow Range

For example, if your device is a 500 ccm full-scale unit and you wish to apply a

set-point of 125 ccm you would enter the following value:

16000 = (125 ccm X 64000) / Full Scale Flow Range

If the controller is in polling mode as described in Changing from Streaming

Mode to Polling Mode, the set-point must be preceded by the address of the

controller. For example, if your controller has been given an address of D, the

set-point above would be sent by typing:

D16000 followed by “Enter”

This manual is related to the following products: