Precision air conditioning, Smartcool, Air cooled models – Airedale SmartCool 11-233kW User Manual
Page 65: T ec hn ic al, X2x2), Performance data – air cooled models, Cooling duties standard condenser match
![background image](/manuals/370926/65/background.png)
Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
65
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Air Cooled Models
(X2X2)
Performance Data – Air Cooled Models
Cooling Duties
Standard Condenser Match
X2X2
Ambient Temperature (°C)
Model
Air On °C DB
25
30
35
40
46
%RH
TC
(KW)
SC
(KW)
TC
(KW)
SC
(KW)
TC
(KW)
SC
(KW)
TC
(KW)
SC
(KW)
TC
(KW)
SC
(KW)
SC19D055-X2X2-0
2 x CR50
22/50
52.4
48.8
52.4
48.8
51.7
48.5
49.1
47.4
45.7
45.7
24/45
53.5
52.4
53.5
52.4
52.8
52.0
50.2
50.2
46.7
46.7
26/40
54.5
54.5
54.5
54.5
53.7
53.7
51.1
51.1
47.6
47.6
SC19D070-X2X2-0
2 x CR65
22/50
65.2
59.8
65.2
59.8
64.9
59.6
62.2
58.4
58.7
56.9
24/45
66.9
64.2
66.9
64.2
66.5
64.1
63.7
63.0
60.1
60.1
26/40
68.3
68.3
68.3
68.3
67.9
67.9
65.0
65.0
61.4
61.4
SC19D080-X2X2-0
2 x CR65
22/50
74.2
67.2
74.2
67.2
73.1
66.7
69.8
65.3
65.7
63.5
24/45
76.1
72.2
76.1
72.2
74.9
71.6
71.5
70.2
67.3
67.3
26/40
77.7
77.6
77.7
77.5
76.3
76.3
72.9
72.9
68.7
68.7
SC25D080-X2X2-0
2 x CR65
22/50
75.7
69.8
75.7
69.8
74.4
69.2
71.1
67.5
66.9
65.4
24/45
77.6
75.1
77.6
75.1
76.2
74.4
72.8
72.7
68.5
68.5
26/40
79.3
79.3
79.3
79.3
77.7
77.7
74.3
74.3
70.0
70.0
SC25D090-X2X2-0
2 x CR65
22/50
82.4
76.5
82.4
76.5
80.4
75.6
76.8
73.8
72.1
71.6
24/45
84.6
82.3
84.6
82.3
82.3
81.2
78.6
78.6
73.9
73.9
26/40
86.4
86.4
86.4
86.4
84.0
84.0
80.2
80.2
75.5
75.5
SC25D100-X2X2-0
2 x CR80
22/50
93.9
85.6
93.9
85.6
92.1
84.6
88.0
82.6
82.8
80.0
24/45
96.3
91.7
96.3
91.7
94.3
90.7
90.1
88.7
84.8
84.8
26/40
98.3
98.3
98.3
98.3
96.1
96.1
91.9
91.9
86.5
86.5
SC31D100-X2X2-0
2 x CR80
22/50
95.8
86.2
95.8
86.2
93.6
85.2
89.3
83.1
83.7
80.4
24/45
98.3
92.5
98.3
92.5
95.9
91.4
91.5
89.4
85.8
85.8
26/40
100.3
99.3
100.3
99.3
97.8
97.8
93.3
93.3
87.7
87.7
SC31D120-X2X2-0
2 x CR105
22/50
109.6
99.1
109.6
99.1
109.0
98.8
104.1
96.5
97.9
93.6
24/45
112.4
106.4
112.4
106.4
111.6
106.0
106.7
103.9
100.4
100.4
26/40
114.8
114.4
114.8
114.4
113.9
113.9
108.9
108.9
102.5
102.5
SC31D130-X2X2-0
2 x CR105
22/50
117.2
105.7
117.2
105.7
115.9
105.1
110.9
102.8
104.5
99.9
24/45
120.2
113.4
120.2
113.4
118.7
112.7
113.6
110.5
107.0
107.0
26/40
122.8
122.1
122.8
122.1
121.2
121.2
116.0
116.0
109.3
109.3
TC=Total Cooling SC=Sensible Cooling
(1) All data quoted is gross
(2) Deduct fan gain for nett duties, refer to Mechanical Data
T
ec
hn
ic
al