Smartcool, Precision air conditioning, W 2 f0 – Airedale SmartCool 11-233kW User Manual
Page 128: Mechanical data – w2f0 continued
![background image](/manuals/370926/128/background.png)
SmartCool
TM
- D
Precision Air Conditioning
128
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Mechanical Data – W2F0 Continued
SC25D045-W2F0
SC25D050-W2F0
SC25D055-W2F0
Standard Dry Cooler Match
1 x DR55
1 x DR70
1 x DR70
Capacity
Nom Cooling (Gross) – W2
(1)
kW
43.8
47.8
54.6
Nom Cooling (Gross) - F0 (Free Cooling)
(2)
kW
91.4
98.8
105.8
Total Heat of Rejection –W2
kW
54.5
60.2
68.9
Capacity Steps
2
2
3
Fan Gain
(5)
kW
2.24
2.65
3.01
Dimensions - W x D x H
mm
2549 x 890 x 1980
2549 x 890 x 1980
2549 x 890 x 1980
Weight - Machine / Operating
kg
980 / 1020
1050 / 1090
1050 / 1100
Construction
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL 7021)
Material/Colour
Frame: Anodised Aluminium Frame with Black Nylon Corners
Evaporator
Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages
2/1
3/1
3/1
Condenser
(3)
Stainless steel Brazed Plate
Water Volume
l
6.1
9.9
9.9
Glycol Flow
l/s
2.66
3.0
3.4
Pressure Drop Condenser
kPa
69
29.8
38.4
Glycol Coil
Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Water Volume
l
42.2
42.2
42.2
Glycol Flow
l/s
3.6
3.8
4
Pressure Drop F0
kPa
75.8
90.3
114.4
Unit
Water flow
l/s
2.66
3.0
3.4
Pressure drop
kPa
144.8
120.1
152.8
Dry Cooler
Water Volume
L
55.9
55.9
55.9
Flowrate
l/s
2.66
3.0
3.4
Pressure Drop
kPa
35.7
48.6
59.3
Fan Motor
Backwards Curved, Centrifugal direct drive
Motor Type
AC
AC
AC
Quantity x Motor Size
kW
3 x 2.38
3 x 2.38
3 x 2.38
Speed @25Pa ESP/ maximum ESP
rpm
1092 / 1364
1220 / 1364
1364 / 1364
Maximum ESP
Pa
328
188
20
Nominal Airflow
m³/s
5.3
5.9
6.5
Compressor - Scroll
Configuration
Dual Cool - Circuit 1 Tandem Compressors (Water Cooled)
Circuit 2 Free Cooling
Quantity - W2
2
Oil Charge Volume - W2
l
2 x 1.57
2 x 3
2 x 3
Oil Type
Polyolvinyl
Polyolester
Connections
Water Inlet / Outlet – W2
mm
42
42
42
Glycol Connections Inlet/Outlet – F0
mm
42
42
42
Condensate Drain Hose
mm
22
22
22
Filtration
Disposable to BS EN 779-G4
Quantity
4
3
3
OPTIONAL EXTRAS
Hot Gas Reheat - X
Nom Heating (Gross)
kW
11.9
12.2
12.2
Electric Heating (Total)
kW
21
21
21
Humidifier
Capacity
kg/hr
8
8
8
Feed/Drain
3/4" BSPF Braided flexible hose / 19mm hose connection
Condensate Pump
Head
m
10.8
10.8
10.8
Flow
l/m
5
5
5
Drain
10mm Stainless Steel Stub Connection
First upgrade Fan Motor - EC Motor
Backwards Curved, Centrifugal direct drive
Quantity x Motor Size
kW
3 x 2.2
3 x 2.2
3 x 2.2
Speed @ 25Pa / maximum ESP
rpm
1074 / 1360
1200 / 1360
1337 / 1360
Maximum ESP
Pa
314
188
45
Fan Gain
(5)
kW
1.4
1.92
2.6
Second upgrade Fan Motor - EC Motor
Backwards Curved, Centrifugal direct drive
Quantity x Motor Size
kW
3 x 3.1
3 x 3.1
3 x 3.1
Speed @ 25Pa / maximum ESP
rpm
1095 / 1520
1225 / 1520
1354 / 1520
Maximum ESP
Pa
464
337
195
Fan Gain
(5)
kW
1.4
1.92
2.6
Low Pressure Hot Water
(4)
Copper Tube/Aluminium Fin
Capacity Gross
kW
32.5
34.1
35.7
Water Flow (Nominal)
l/s
0.72
0.76
0.79
Pressure Drop
kPA
20.2
21
21.8
LPHW Connection Sizes
mm
22
22
22
(1) Entering air 24°C/ 45% RH condenser water in / out 35 / 40°C
(2) Entering air 24°C/ 45% RH condenser water in / out 7/12°C and based on water.
(3) Pressure drop through condenser, free cooling coil, 3 port valve, Head pressure control valve and unit pipe work
(4) Based upon low pressure hot water 82°C inlet/71°C outlet. Air on 20°C
(5) Fan gain based on 25Pa ESP @ nominal air volume. Fan gain will change as airflow and ESP change.
W
2