Installation, Maintenance and Commissioning Manual :6877419 02/2013
Model
Fan
Selection
Standard
Air
Volume
(m³/s)
DeHum
Air
Volume
(m³/s)
Max Air
Volume
(m³/s)
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
SC25D090-X2X2-0
AC SC25D
STD
5.85
8.8
8.9
9.1
9.3
9.4
9.6
9.8
9.9
-
-
-
-
2.93
4.6
4.9
5.3
5.5
5.7
6.0
6.2
6.4
6.6
6.8
7.1
7.3
7.75
-
-
-
-
-
-
-
-
-
-
-
-
EC SC25D
STD
5.85
8.1
8.3
8.5
8.6
8.8
8.9
9.1
9.3
9.4
9.6
9.8
10.
0
2.93
4.3
4.6
4.9
5.2
5.5
5.7
6.0
6.3
6.6
6.9
7.1
7.3
7.75
-
-
-
-
-
-
-
-
-
-
-
-
EC SC25D
UPG
5.85
7.6
7.7
7.9
8.0
8.2
8.3
8.4
8.6
8.7
8.9
9.0
9.1
2.93
3.9
4.3
4.6
4.9
5.1
5.4
5.6
5.8
6.0
6.2
6.4
6.7
7.75
9.9
-
-
-
-
-
-
-
-
-
-
-
SC25D100-X2X2-0
AC SC25D
STD
6.50
9.7
9.9
-
-
-
-
-
-
-
-
-
-
3.25
5.1
5.4
5.6
5.9
6.1
6.3
6.5
6.8
7.0
7.2
7.4
7.6
7.75
-
-
-
-
-
-
-
-
-
-
-
-
EC SC25D
STD
6.50
9.0
9.1
9.3
9.4
9.6
9.8
9.9
-
-
-
-
-
3.25
4.7
5.0
5.3
5.5
5.8
6.1
6.4
6.6
6.9
7.2
7.4
7.5
7.75
-
-
-
-
-
-
-
-
-
-
-
-
EC SC25D
UPG
6.50
8.4
8.5
8.7
8.8
8.9
9.1
9.2
9.3
9.4
9.6
9.7
9.8
3.25
4.3
4.6
5.0
5.2
5.4
5.6
5.8
6.1
6.3
6.5
6.7
6.9
7.75
9.9
-
-
-
-
-
-
-
-
-
-
-
SC31D100-X2X2-0
EC SC31D
UPG
6.11
7.6
7.8
7.9
8.0
8.2
8.3
8.4
8.6
8.7
8.8
9.0
9.1
3.06
3.9
4.2
4.5
4.8
5.1
5.3
5.5
5.8
6.0
6.2
6.4
6.6
8.00
9.9
10
-
-
-
-
-
-
-
-
-
-
SC31D120-X2X2-0
EC SC31D
UPG
7.33
9.1
9.2
9.3
9.4
9.5
9.7
9.8
9.9
10.
0
-
-
-
3.67
4.7
5.0
5.2
5.4
5.6
5.8
6.0
6.3
6.5
6.7
6.9
7.1
8.00
9.9
10
-
-
-
-
-
-
-
-
-
-
SC31D130-X2X2-0
EC SC31D
UPG
7.94
9.8
9.9
-
-
-
-
-
-
-
-
-
-
3.97
5.1
5.3
5.5
5.7
5.9
6.1
6.3
6.5
6.7
6.9
7.1
7.3
8.00
9.9
10.
0
-
-
-
-
-
-
-
-
-
-
In
s
ta
ll
a
ti
on