Precision air conditioning, Smartcool, W 2 c0 – Airedale SmartCool 11-233kW User Manual
Page 117: Electrical data- w2c0 continued

Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
117
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data- W2C0 Continued
SC31D055-W2C0-0
SC31D065-W2C0-0
SC31D075-W2C0-0
Standard Dry Cooler Match
1 x DR70
1 x DR95
1 x DR95
Unit Data Full Function- W2C0
Nominal Run Amps
(1)
A
84.2
84.4
84.4
Maximum Start Amps
A
177.9
197.5
211.1
Recommended Mains Fuse Size
A
100
100
100
Max Mains Incoming Cable Size
mm²
35
70
70
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling Only - W2C0
Nominal Run Amps
A
56.2
56.4
58.7
Maximum Start Amps
A
169.3
169.4
202.4
Recommended Mains Fuse Size
A
63
63
80
Evaporator Fan Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
(2)
kW
3 x 3.1
3 x 3.1
3 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Compressor 1 , Circuit 1
Motor Size
(3)
kW
7.2
9.5
9.5
Nominal Run Amps
A
12.9
16.9
16.9
Locked Rotor Amps
A
92
130
130
Type of Start
Direct On Line
Compressor 2, Circuit 1
Motor Size
kW
9.5
9.5
10.86
Nominal Run Amps
A
16.9
16.9
19.2
Locked Rotor Amps
A
130
130
163
Type of Start
Direct On Line
Standard Dry Cooler Match - Motor Per Fan
AC
EC
EC
Quantity x Motor Size
(2)
kW
4 x 0.6
4 x 0.88
4 x 0.88
Full Load Amps
A
2.62
1.65
1.65
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat
3
3
3
Number of Elements
9
9
9
Rating (Total)
kW
31.5
31.5
31.5
Current Per Phase
A
45.5
45.5
45.5
Humidifier
Capacity
kg/hr
8
8
8
Rating
kW
6
6
6
Full Load Amps
A
8.7
8.7
8.7
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
(2)
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size
(2)
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Dry Cooler Match - EC Motor-Per Fan
Quantity x Motor Size
(2)
kW
4 x 0.73
4 x 1.68
4 x 1.68
Full Load Amps
A
3.3
2.6
2.6
Dry Cooler Match - SCAF Fan
Quantity x Motor Size
(2)
kW
4 x 1.4
4 x 1.94
4 x 1.94
Full Load Amps
A
6
3.4
3.4
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed