Smartcool, Precision air conditioning, C 000 – Airedale SmartCool 11-233kW User Manual
Page 150
![background image](/manuals/370926/150/background.png)
SmartCool
TM
- D
Precision Air Conditioning
150
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Waterside Pressure Drop C000
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
160.00
180.00
200.00
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
Flow Rate (l/s)
P
ress
u
re
D
ro
p
(
kPa)
1
2
4
3
1 SC19D065 – 075
2
SC19D090
3
SC25D090 – 110
4
SC31D110 - 150
(1)
Includes coil, 3 port valve and pipework.
(2)
To calculate 3 port valve pressure drop:
DP valve =
2
ч
ш
ц
з
и
ж
M
Q
where
DP = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =
ч
ш
ц
з
и
ж
36
Kv
(3)
Fluid 100% water.
M Values
Model Sizes
SC19D65-75
SC19D90
SC25D90-110
SC31D110-150
Chilled Water “M” Valve
0.8
1.11
1.11
1.11
C