Smartcool, Precision air conditioning – Airedale SmartCool 11-233kW User Manual
Page 38
![background image](/manuals/370926/38/background.png)
SmartCool
TM
- D
Precision Air Conditioning
38
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Model
Fan
Selectio
n
Standard
Air
Volume
(m³/s)
DeHum
Air
Volume
(m³/s)
Max Air
Volume
(m³/s)
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
SC19D055-X2X2-0
EC
SC19D
STD
3.48
6.4
6.7
7.1
7.2
7.4
7.6
7.7
7.9
8.1
8.2
8.4
8.6
1.74
3.6
3.9
4.2
4.5
4.8
5.1
5.4
5.7
6.0
6.3
6.6
6.9
5.50
-
-
-
-
-
-
-
-
-
-
-
-
EC
SC19D
UPG
3.48
6.2
6.4
6.6
6.7
6.9
7.0
7.2
7.4
7.5
7.7
7.8
8.0
1.74
3.3
3.6
3.9
4.2
4.5
4.8
5.1
5.3
5.5
5.8
6.0
6.2
5.50
9.6
9.7
9.8
9.9
-
-
-
-
-
-
-
-
SC19D070-X2X2-0
EC
SC19D
STD
4.43
8.3
8.4
8.6
8.7
8.9
9.0
9.2
9.3
9.5
9.6
9.8
10.
0
2.22
4.3
4.6
4.9
5.2
5.4
5.7
6.0
6.3
6.5
6.8
7.1
7.3
5.50
-
-
-
-
-
-
-
-
-
-
-
-
EC
SC19D
UPG
4.43
7.8
8.0
8.1
8.2
8.3
8.5
8.6
8.7
8.8
9.0
9.1
9.2
2.22
3.8
4.2
4.5
4.8
5.1
5.3
5.5
5.8
6.0
6.2
6.4
6.6
5.50
9.6
9.7
9.8
9.9
-
-
-
-
-
-
-
-
SC19D080-X2X2-0
EC
SC19D
STD
5.06
9.4
9.6
9.7
9.9
-
-
-
-
-
-
-
-
2.53
4.8
5.1
5.4
5.6
5.9
6.1
6.4
6.7
6.9
7.2
7.3
7.5
5.50
-
-
-
-
-
-
-
-
-
-
-
-
EC
SC19D
UPG
5.06
8.9
9.0
9.1
9.2
9.4
9.5
9.6
9.7
9.8
9.9
-
-
2.53
4.4
4.8
5.1
5.3
5.5
5.7
5.9
6.1
6.3
6.5
6.7
6.9
5.50
9.6
9.7
9.8
9.9
-
-
-
-
-
-
-
-
SC25D080-X2X2-0
AC
SC25D
STD
5.20
7.8
8.1
8.3
8.4
8.6
8.8
8.9
9.1
9.3
9.4
9.6
9.8
2.60
4.1
4.4
4.8
5.1
5.4
5.6
5.8
6.1
6.3
6.5
6.7
6.9
7.75
-
-
-
-
-
-
-
-
-
-
-
-
EC
SC25D
STD
5.20
7.3
7.5
7.7
7.8
8.0
8.2
8.4
8.5
8.7
8.9
9.0
9.2
2.60
3.9
4.2
4.5
4.8
5.1
5.4
5.7
6.0
6.3
6.6
6.9
7.2
7.75
-
-
-
-
-
-
-
-
-
-
-
-
EC
SC25D
UPG
5.20
6.8
7.0
7.1
7.3
7.5
7.6
7.8
7.9
8.1
8.2
8.4
8.5
2.60
3.6
3.9
4.2
4.6
4.9
5.1
5.3
5.6
5.8
6.0
6.2
6.4
7.75
9.9
-
-
-
-
-
-
-
-
-
-
-
In
s
ta
ll
a
ti
on