6.1.2 In Circuit, LC-110H Loop Power
In “mA Measure with 24V” mode the LC-110H is in circuit and the
loop power is supplied by the LC-110H as shown below.

(+)

(–)

MARTEL ELECTRONICS

LC-110H

Precision Loop

Calibrator w/HART™

100%

25%

0%

MENU

EXIT

Measure 24V

0.00%

4.000mA

250

Note: In this situation the 250

Ω HART resistor is enabled. If your loop

already has 250

Ω, do not enable the HART resistor.

6.1.3 Across Circuit, Communicator Only
In “Communicator Only” mode the LC-110H is across the circuit and
the loop power is supplied externally as shown below.

MARTEL ELECTRONICS

LC-110H

Precision Loop

Calibrator w/HART™

100%

25%

0%

MENU

EXIT

PT12234

Device Setup & Data
Write LRV & URV Value
Trim, Set, & Zero
Device Diagnostic
Data Log & Config Log

24V

SUPPLY

(+)

(–)

4 to 20mA

RL≥250Ω

Note: In the Communicator Only Mode, there must be 250

Ωs

resistance present in the loop.