beautypg.com

KROHNE BM 90 EN User Manual

Page 32

background image

32

4.6.

Open channel flowmeter (Pr.1 = 4)

with penstock control

The application :

l

As chapter 4.5. but additionally to control a penstock via Relays 1 and 2 to modulate flow

between 25 and 30 l/s

ENTER:

Pr.1 - Pr.6 as example 5, then go to Pr.9

Pr.9 =

30

Defines top flow limit 30 litres per second.

Pr.10

=

25

Defines low flow limit 25 litres per second.

Pr.12

=

8

Duration of penstock drive pulse is 8 seconds.

Pr.13

=

4

Time between drive pulses is 4 seconds.

ENTER:

Pr.14 - Pr.48 as example 5, then go to Pr.50.

Pr.50

=

2

To initiate penstock control.

ENTER:

Pr.78 and Pr.98 as example 5.