Examples, 1 level measurement mode (pr.1 = 1) – KROHNE BM 90 EN User Manual

Page 27

background image

27

4. Examples

4.1 Level measurement mode (Pr.1 = 1)

Applications for this mode are Level Measurement, Contents Measurement and Pump Control.

The application :

l

To measure and display the level of liquid in meters

l

Maximum level 3 m,

l

Fill rate 0.1 meter/min

l

Alarm if level exceeds 2.8 m

l

0-20 mA signal proportional to level

Pr. 1

=

1

Defines level measurement.

Pr. 2

=

2

Programme units are meters.

Pr. 3

=

4

Distance of transducer from the zero level.

Pr. 4

=

3

The span, based on zero level.

Pr. 5

=

0.5

Blanking zone into which level should not rise.

Pr. 6

=

0.1

The maximum rate of change of liquid level in meters/min.

Pr. 8

=

1

Relay 1 to alarm on level (normally energised).

Pr. 9

=

2.8

Relay 1 de-energised at 2.8 m indicates high alarm.

Pr.10

=

2.6

Relay 1 re-energised at 2.6 m to clear the high alarm.

Pr.23

=

3

Hold alarm indication (relay 1) on failsafe.

Pr.28

=

3

Analogue output holds on failsafe.

Pr.30

=

3

0.20 mA output fixed to span (Pr.4).

Pr.78

Simulate the program.

3.0m

(Pr.4)

4.0m

(Pr.3)

Reset

Alarm

2.8m

(Pr.9)

Set

Alarm

0.5m

(Pr.5)

2.6m

(Pr.10)