KROHNE BM 90 EN User Manual
Page 20
20
Pr. 29 Failsafe Time Delay (D=120)
Enter value (in seconds) before unit goes to selected fail-
safe positions.Minimum value is 30 seconds.
Pr. 23 Relay 1
Failsafe)
Pr. 24 Relay 2
Failsafe
)
Pr. 25 Relay 3
Failsafe
)
Pr. 26 Relay 4
Failsafe
)
Pr. 27 Relay 5
Failsafe
)
Note :
Relay designated LOSS-OF-ECHO will always
de-energise.
Relay 5 Failsafe is not applicable in differential or OCM
mode.
Enter 1
Energise
2
De-energise
3
Hold-state
one option for each relay
Pr. 28 Analogue and Display Failsafe (D=3)
Enter
1 Low
2 High
3 Hold
Value
Level/Differential
Enter values in display unit as
selected Pr. 2.
Flow
Enter values in unit selected at
Pr.46
Temperature
Enter values in C
(only valid if probe fitted)
Sampler
Enter value in hours
(no reset needed)
Totalizer
Refer to Pr.49
Loss of Echo
No set/Reset entries are required
or run/prog
Pr. 20 Relay 5 Designation - Basic Application - Relay Function
Pr. 21 Relay 5 Set
Pr. 22 Relay 5 Reset
Pr.23 to 27
Failsafe (D=3 for all)
On loss of power all relays will de-energise.
For other fault conditions e.g. damaged transducer, the
failsafe relay state (after time delay selected at Pr. 29) is
selectable.
(e)
normally energised
(d)
normally de-energised
de-energised to alarm
energise to start (motor)
Relay 5
Pr. 1 = 1 / Pr.1 = 2
Pr. 1 = 3
Pr. 1 = 4
Designation
Level / Distance
Differential
Open Channel Flow
Enter
0
Off
N / A
Off
1
Level Alarm
(e)
N / A
Level Alarm
(e)
2
Level Control
(d)
N / A
Level Control
(d)
3
Off
N / A
Flow Alarm
(e)
4
Off
N / A
Off
5
Off
N /A
Totalizer Drive
(d)
6
Temperature Alarm
(e)
N / A
Temp. Alarm
(e)
7
Loss of Echo
(e)
N / A
Loss of Echo
(e)
8
Run / Prog
(e)
N / A
Run / Prog
(e)