Pr. 29 Failsafe Time Delay (D=120)

Enter value (in seconds) before unit goes to selected fail-

safe positions.Minimum value is 30 seconds.

Pr. 23 Relay 1

Failsafe)

Pr. 24 Relay 2

Failsafe

)

Pr. 25 Relay 3

Failsafe

)

Pr. 26 Relay 4

Failsafe

)

Pr. 27 Relay 5

Failsafe

)

Note :

Relay designated LOSS-OF-ECHO will always

de-energise.

Relay 5 Failsafe is not applicable in differential or OCM

mode.

Enter 1

Energise

2

De-energise

3

Hold-state

one option for each relay

Pr. 28 Analogue and Display Failsafe (D=3)

Enter

1 Low

2 High

3 Hold

Value

Level/Differential

Enter values in display unit as

selected Pr. 2.

Flow

Enter values in unit selected at

Pr.46

Temperature

Enter values in C

(only valid if probe fitted)

Sampler

Enter value in hours

(no reset needed)

Totalizer

Refer to Pr.49

Loss of Echo

No set/Reset entries are required

or run/prog

Pr. 20 Relay 5 Designation - Basic Application - Relay Function

Pr. 21 Relay 5 Set

Pr. 22 Relay 5 Reset

Pr.23 to 27

Failsafe (D=3 for all)

On loss of power all relays will de-energise.

For other fault conditions e.g. damaged transducer, the

failsafe relay state (after time delay selected at Pr. 29) is

selectable.

(e)

normally energised

(d)

normally de-energised

de-energised to alarm

energise to start (motor)

Relay 5

Pr. 1 = 1 / Pr.1 = 2

Pr. 1 = 3

Pr. 1 = 4

Designation

Level / Distance

Differential

Open Channel Flow

Enter

0

Off

N / A

Off

1

Level Alarm

(e)

N / A

Level Alarm

(e)

2

Level Control

(d)

N / A

Level Control

(d)

3

Off

N / A

Flow Alarm

(e)

4

Off

N / A

Off

5

Off

N /A

Totalizer Drive

(d)

6

Temperature Alarm

(e)

N / A

Temp. Alarm

(e)

7

Loss of Echo

(e)

N / A

Loss of Echo

(e)

8

Run / Prog

(e)

N / A

Run / Prog

(e)