The application - relay function options are shown on the following tables : (D = 0 or 0.00 for all)

Pr. 9

Relay 1 Set

Pr. 10 Relay 1 Reset

Pr. 11 Relay 2 Designation

Pr. 12 Relay 2 Set

Identical to Pr. 8.

Identical to Pr. 9.

Pr. 13 Relay 2 Reset

Identical to Pr. 10.

Pr. 8 Basic A pplication - Relay Function 1 - 2

(e)

normally energised

(d)

normally de-energised

de-energised to alarm

energise to start (motor)

Relay 1

Pr. 1 = 1 / Pr.1 = 2

Pr. 1 = 3

Pr. 1 = 4

Designation

Level / Distance

Differential

Open Channel Flow

Enter

0

Off

Off

Off

1

Level Alarm

(e)

Level Alarm on

(e)

Level Alarm

(e)

either transducer

2

Level Control

(d)

Differential Alarm

(e)

Level Control

(d)

3

Off

Differential Control

(d)

Flow Alarm

(e)

4

Off

Downstream Level

(e)

Off

Alarm

5

Off

Upstream Level Alarm

(e)

Off

6

Temperature Alarm

(e)

Temperature Alarm

(e)

Temperature Alarm

(e)

7

Loss of Echo

(e)

Loss of Echo

(e)

Loss of Echo

(e)

8

Run / Prog

(e)

Run / Prog

(e)

Run / Prog

(e)

Level/Differential

Enter values in display unit as

selected Pr. 2.

Flow

Enter values in unit selected at

Pr.46

Temperature

Enter values in C

(only valid if probe fitted)

Loss of Echo

No set/Reset entries are required

or run/prog

Pr. 15 Relay 3 Set

Pr. 16 Relay 3 Reset

Pr. 17 Relay 4 Designation

Identical to Pr. 8.

Pr. 18 Relay 4 Set

Identical to Pr.9.

Pr. 19 Relay 4 Reset

Identical to Pr.10.

Pr. 14 Relay 3 Designation

Identical to Pr. 8.

Identical to Pr. 9.

Identical to Pr. 10.