2 passwords, 3 configuration database – KROHNE VFM 3100 EN User Manual
Page 22
22
2. Operating the VFM 3100
2.1 Introduction
Communication with the VFM 3100 is carried out using the HART
Model 275 Communicator or the optional Local Digital Display/Con-
figurator. General instructions for using the HART Configurator can
be found in MAN 4250, HART Communicator Product Manual.
Vortex-specific instructions for using the HART configurator will be
found in chapter 8 of this document. Complete instructions for using
the Local Configurator will be found in chapter 9.
Note: For proper communication with VFM 3100, the HART
configurator must contain the DD for the KROHNE VFM 3100.
This DD is available from KROHNE, or any other authorized HART
Foundation source.
2.2 Passwords
The transmitter itself has no password. Rather, security measures,
i.e., the ability to access functions such as calibration, configuration,
and testing, are associated with the configurators used to communi-
cate with the transmitter. The HART Communicator has no security
measure other than access to the device itself. The Local Digital Dis-
play/Configurator requires a password that is user definable. See
chapter 9.
2.3 Configuration Database
In order to function, the transmitter requires specific embedded
information, termed the “configuration database”. The parameters in
this database are listed in Table 8, and defined in chapter 9.
Each VFM 3100 is shipped from the factory with an operating confi-
guration database; however, the VFM 3100 will not provide an accu-
rate measurement if the configuration does not fit the application.
Be sure to check the configuration of each VFM 3100 prior
to start-up!
Flowtube Parameters
Model Code
Meter Body Serial Number
Reference K-Factor
Identification Parameters
Tag
Descriptor
Date
Message
Polling Address
Transmitter Options
Flow Units
Total Units
Noise Rejection
Signal Conditioning
Low Flow Correction
Low Flow Cut-In
Process Fluid Parameters
Fluid Type
Process Temperature
Process Density
Base Density
Process Viscosity
Application Parameters
Mating Pipe
Piping Configuration
Upstream Distance
Custom K-factor Bias
Upper Range Value
Output Options
Damping Value
Pulse Output
AO/PO Alarm Type
Table 8. Configuration Database
Tag
Fluid Type
Flow Units
Total Units
Process Temperature (value and units)
Process Density (value and units)
Base Density (if applicable; value)
Process Viscosity (if applicable; value and units)
Upper Range Value
Table 9. User Information
In all cases, the factory configuration includes the VFM 3100 Model
Code, Meter Body Serial Number, and Reference K-Factor.
It also includes the User Information in Table 9, if supplied with
the purchase order.