B.67

[SOURce:]VOLTage:PROTection:TRIPped?

QUERY

VOLT:PROT:TRIP?

Syntax:

Short Form: [SOUR:]VOLT:PROT:TRIP? Long Form: [SOURce:]VOLTage:PROTection:TRIPped?
Return Value: 0 or 1

Description: Identifies whether overvoltage condition was detected. Returns 0 if overvoltage protection

tripped; 1 if overvoltage protection not tripped. Related Commands: VOLT:PROT, VOLT:PROT:CLE.
(See example, Figure B-6.)

B.68

[SOURce:]FUNCtion:MODE?

QUERY

FUNC:MODE?

Syntax:

Short Form: FUNC:MODE?

Long Form: [SOURce:]FUNCtion:MODE?

Return Value: VOLT or CURR

Description: Identifies the operating mode of the power supply. VOLT = Constant Voltage mode (CV).

CURR = Constant Current mode (CC). (See example, Figure B-1.)

B.69

STATus:OPERation:CONDition

QUERY

STAT:OPER:COND?

Syntax:

Short Form: STAT:OPER:COND?

Long Form: STATus:OPERation:CONDition?

Return Value: 0 to 1313 (1 + 32 + 256 + 1024).

Description: Returns the value of the Operation Condition Register (see Table B-2). The Operation Condition

Register contains unlatched real-time information about the operating conditions of the power supply.
Bit set to 1 = function enabled (active, true); bit reset to 0 = function disabled (inactive, false). (See
example, Figure B-7.)

B.70

STATus:OPEReration:ENABle

COMMAND

STAT:OPER:ENAB

Syntax:

Short Form:

STAT:OPER:ENAB 0 to 1313 (1 + 32 + 256 + 1024)

Long Form:

STATus:OPERation:ENABle 0 to 1313 (1 + 32 + 256 + 1024)

Description: Sets Operation Enable Register. The Operation Enable Register is a mask for enabling specific bits

in the Operation Event Register which will cause the operation summary bit (bit 7) of the Status Byte
register to be set Bit set to 1 = function enabled (active, true); bit reset to 0 = function disabled (inac-
tive, false). The operation summary bit is the logical OR of all the enabled bits in the Operation Event
register. (See example, Figure B-7.)

B.71

STATus:OPEReration:ENABle?

QUERY

STAT:OPER:ENAB?

Syntax:

Short Form: STAT:OPER:ENAB?

Long Form: STATus:OPERation:ENABle?

Return Value: 0 to 1313 (1 + 32 + 256 + 1024).

Description: Reads Operation Enable Register (see Table B-2). Returns value of Operation Enable Register

bits. Bit set to 1 = function enabled (active, true); bit reset to 0 = function disabled (inactive, false).
(See example, Figure B-7.)

TABLE B-2. OPERATION CONDITION REGISTER, OPERATION ENABLE REGISTER,

AND OPERATION EVENT REGISTER BITS

CONDITION

NU

CC

NU

CV

NU

WTG

NU

CAL

BIT

15-11

10

9

8

7 - 6

5

4 - 1

0

VALUE

32,768 -

2048

1024

512

256

128 - 64

32

16 -2

1

CAL - INTERFACE COMPUTING NEW CALIBRATION

CONSTANTS

CC -

POWER SUPPLY IN CONSTANT CURRENT MODE

CV -

POWER SUPPLY IN CONSTANT VOLTAGE MODE

NU -

NOT USED

WTG WAIT FOR TRIGGER (SET BY INIT SUBSYSTEM)