TABLE 1-3. ABC SPECIFICATIONS

SPECIFICATION

RATING/DESCRIPTION

CONDITION

INPUT CHARACTERISTICS

a-c Voltage

nominal

100/120/220/240V a-c

Single phase

range

85-264V a-c

Wide range

Frequency

nominal

50-60Hz

>63Hz Input leakage current

exceeds specifications

range

47-63Hz (400Hz)

Current

85V a-c

1.8A

Maximum at

100W output

120V a-c

1.3A

240V a-c

0.65A

264V a-c

0.60A

Initial turn-on surge

5A peak for <150 usec

85-264V a-c, 0-100% load

Power Factor (min)

120V

0.99

100% load

240V

0.97

EMC immunity to:

Radiated RF

EN 61000-4-3

level 3

Magnetic Field

EN 61000-4-8

level 4

Electrostatic discharge

EN 61000-4-2

level 2: contact,

level 3: 8KV air discharge

Conducted RF

EN 61000-4-6

level 3

Electrical fast transient

EN 61000-4-4

level 3

Surges

EN 61000-4-5

level 4

EMC Emissions

Conducted

EN 55022 Class B

0.15-30 MHz

Radiated

EN 55022 Class B

30-1000 MHz

Harmonics

Conducted

EN 61000-3-2

0-2 KHz

Leakage current

120V a-c

<0.25mA

Source frequency in

47-63Hz range

240V a-c

<0.5mA

Circuit type

PFC

Flyback converter

Output

Forward converter

Switching Frequency

100KHz

OUTPUT CHARACTERISTICS

Type of Stabilizer

Automatic crossover

Voltage/Current

Adjustment range

0 to 100% of rating

Voltage/Current

Source effect

Voltage

<0.01% E

O

max

Nominal ±15%

of input voltage

Current

<0.01% I

O

max

Load effect

Voltage

<0.01% E

O

max

0 to 100% load change

Current

<0.02% I

O

max

Temperature effect

Voltage

<0.01% E

O

max

Per degree C

(0 to 50° C)

Current

<0.01% I

O

max

Time effect

Voltage

<0.01% E

O

max

0.5-8.5 hours

Current

<0.01% I

O

max

Error sense

0.5V per wire

Voltage allowance

Isolation voltage

500V d-c or peak

Output to ground