beautypg.com

HT instruments VEGA78 User Manual

Page 114

background image

VEGA78

EN - 112

Energy – Single phase / Three phase systems (@ Cos

>0.5 and Vmis>60V, clamp type STD)

Parameter

[Wh, VArh, VAh]

Full Scale

Clamp (FS)

Range

[Wh, VArh, VAh]

Accuracy

Resolution

[Wh, VArh, VAh]

Active Energy

Reactive Energy

Apparent Energy

FS

 1A

0.0

 999.9

1.000

 9.999k

(1.0%rdg+6dgt)

0.1

0.001k

1A< FS

 10A

0.000

 9.999k

10.00

 99.99k

0.001k

0.01k

10A< FS

 100A

0.00

 99.99k

100.0

 999.9k

0.01k

0.1k

100A< FS

 3000A

0.0

 999.9k

1.000

 9.999M

0.1k

0.001M

For STD clamp
Vmis = voltage correspondent to power measurement
FS = Full scale clamp

Power Factor (Cos

) – Single phase / Three phase systems

Range

Accuracy (°)

Resolution (°)

0.20

0.50

1.0

0.01

0.50

0.80

0.7

0.80

1.00

0.6

Voltage / Current harmonics

Range Accuracy(*)

Resolution

DC

 25

a

(5.0%rdg+5dgt)

0.1V / 0.1A

26

a

 33

a

34

a

 49

a

(*) Accuracy to add at correspondent TRMS paramters

Frequency

Range Accuracy

Resolution

42.5

69.0Hz

(0.2%rdg+1dgt)

0.1Hz