VEGA78
EN - 98
In this page, the following symbols are used:
Patt
System total Active Power
Preatt
Total Reactive Power
Papp
Total Apparent Power
Pf
Total Power Factor
CosPhi
System total CosPhi
CosPhi represents the theoretical limit value which
can be reached by the Power factor if all harmonics
are eliminated from the electrical system. For
dimensioning a power factor correction system,
reference is usually made to the CosPhi parameter
value.
Fig. 166: Page 2/5 of numeric values for three-phase 3-wire system
The following keys are active on this page:
The F1 key (or the PAG item on the display) advances to the following page of saved
values.
The ESC key (or the smart icon on the display) to exit the function and go back to the
“Recording analysis” page (Fig. 124).
In this page, the following symbols are used:
V1PE
Phase L1 - PE Voltage
I1
Phase L1 Current
Patt1
Phase L1 Active Power
Preatt1
Phase L1 Reactive Power
Papp1
Phase L1 Apparent Power
Pf1
Phase L1 Power Factor
CosPhi1
Cosine of the phase delay between the Phase L1
voltage and current fundamentals
CosPhi represents the theoretical limit value which
can be reached by the Power factor if all harmonics
are eliminated from the electrical system. For
dimensioning a power factor correction system,
reference is usually made to the CosPhi parameter
value.
Fig. 167: Page 3/5 of numeric values for three-phase 3-wire system
The following keys are active on this page:
The F1 key (or the PAG item on the display) advances to the following page of saved
values.
The ESC key (or the smart icon on the display) to exit the function and go back to the
“Recording analysis” page (Fig. 124).