First fault current – IT systems
Range [mA]
Resolution [mA]
Accuracy
0.1
0.9
0.1
(5
reading+1digit)
1
999
1
(5
reading + 3digits)
Limit contact voltage (ULIM) : 25V, 50V
Test on RCD protection (Molded case type)
Differential protection type (RCD): AC ( ), A (
), B(
) – General (G), Selective (S) and Delayed ( )
Voltage range Phase-Earth, Phase-Neutral: 100V
265V RCD type AC and A, 190V 265V RCD type B
Rated tripping currents (I
N): 10mA, 30mA, 100mA, 300mA, 500mA, 650mA, 1000mA
Frequency:
50/60Hz
5%
Molded case type RCD tripping current - (for General RCD only)
RCD type
I
N Range
I
N
[mA]
Resolution [mA]
Accuracy
AC, A
I
N = 10mA
(0.3
1.1) I
N
0.1I
N
- 0%, +10%I
N
10mA
N
650mA
- 0%, +5%I
N
B
30mA
IN 100mA
Measurement duration of Molded case type RCD tripping time – TT/TN systems
x 1/2
x 1
x 2
x 5
AUTO
\ G
S G S
G S
G S
G S
G S
10mA
AC 999 999 999 999 999 999 200 250
50 150
310
A 999 999 999 999 999 999 200 250
50 150
310
B
30mA
100mA
AC 999 999 999 999 999 999 200 250
50 150
310
A 999 999 999 999 999 999 200 250
50 150
310
B 999 999 999 999 999 999
310
300mA
AC 999 999 999 999 999 999 200 250
50 150
310
A 999 999 999 999 999 999 200 250
50 150
310
B 999 999 999 999 999 999
500mA
650mA
AC 999 999 999 999 999 999 200 250
50 150
310
A 999 999 999 999 999 999 200 250
310
B
1000mA
AC 999 999 999 999 999 999 200 250
A 999 999 999 999 999 999
B
Table with duration of tripping time measurement [ms] - Resolution: 1ms, Accuracy:
(2.0
reading + 2digits)
Measurement duration of Molded case type RCD tripping time – IT systems
x 1/2
x 1
x 2
x 5
AUTO
\ G
S G S
G S
G S
G S
G S
10mA
AC 999 999 999 999 999 999 200 250
50 150
310
A
B
30mA
100mA
300mA
AC 999 999 999 999 999 999 200 250
50 150
310
A
B
500mA
650mA
AC 999 999 999 999 999 999 200 250
50 150
310
A
B
1000mA
AC 999 999 999 999 999 999 200 250
A
B
Table with duration of tripping time measurement [ms] - Resolution: 1ms, Accuracy:
(2.0
reading + 2digits)