Fire-Lite PS-Tools MS-9050 User Manual
Page 87
PS-Tools User Guide
50 Pt Addr Panel
PS-Tools
08/2010
81
3.
Click Manual Evacuate to generate a Drill Activated Trouble at fire panel. The Drill Activated
trouble sounds all Silenceable devices and NACs connected to the FACP.
4.
Click Restore Evacuate to clear the Drill Activated trouble and restore the fire panel to Normal
state. The sounding of the Silenceable devices and the NACs continues. Press Signal Silence
button in the fire panel keypad to stop the sounders and NACs.
5.
Click Trouble Silence to silence all the trouble events in the fire alarm system.
6.
Click Clear History to clear all the History data in the fire panel. For more information about
History Data, see
7.
Click Clear Display to clear the display of the status information in PC Panel
Communication Status.
8.
Click Close to close the Upload/Download dialog box after the upload/download process is
completed.
Options
Downloads option modules information to
the fire panel.
ANN-Bus
Downloads ANN-Bus information to the fire
panel.
Date and Time
Downloads date and time information to the
fire panel.
•
You must enter the time in Download
Date and Time dialog box, to set the
download time.
•
Specify and/or verify the time, and
then click OK.
Table 0-1
Download Options
Options
Function