2) (see, Nac (notification appliance circuits) – Fire-Lite PS-Tools MS-9050 User Manual
Page 38
30
50 Pt Addr Panel
PS-Tools
08/2010
Configuring Fire Panels
NAC (Notification Appliance Circuits)
The notification appliances include speakers, horns, strobes, bells, and other type of sounder
appliances. There are four notification appliance circuits, which can be configured for the 50 Pt Addr
panel.
Figure 5-4
Configuring Notification Appliance Circuits
To configure NAC 1
1.
Click NAC 1 Enabled, to enable NAC 1, If you select Disable, the fire panel prevents the
selected NAC from activating its devices.
2.
Click NAC 1 - 1 Minute Silence Inhibit Enabled, to enable the silencing of the audible
devices in NAC 1, only after 60 seconds. If this option is enabled, the audible devices can be
silenced by pressing the Alarm Silence key, only after 60 seconds.
3.
Click NAC 1 - Silenceable, to indicate if the notification appliance can be silenced by pressing
the Alarm Silence key. If the Silenceable option is not enabled, the selected NACs cannot be
silenced by pressing the Alarm Silence key or by the Auto Silence feature.
4.
Select the delay for NAC 1 Auto Silence from the list, to automatically silence the main circuit
board silenceable NACs after a programmed length of time. This option is disabled if the
Silenceable option is not selected.
5.
Select the NAC 1 Coding option to specify the type of output the main circuit board
notification appliances generates, when activated. For more information about each coding
selection, see
6.
Select the NAC 1 Type Code from the list.