Installation precautions – Fire-Lite PS-Tools MS-9050 User Manual
Page 3

A fire alarm system does not operate without 
any electrical power. If AC power fails, the 
system operates from standby batteries only for a 
specified time and only if the batteries are 
properly maintained and replaced regularly. 
Equipment used in the system may not be 
technically compatible with the control panel. It is 
essential to use only equipment listed for service 
with your control panel. 
Telephone lines needed to transmit alarm 
signals from a premise to a central monitoring 
station may be out of service or temporarily 
disabled. For added protection against telephone 
line failure, backup radio transmission systems 
are recommended. 
The most common cause of fire alarm 
malfunction is inadequate maintenance. To keep 
the entire fire alarm system in excellent working 
order, ongoing maintenance is required per the 
manufacturer's recommendations, and UL and 
NFPA standards. 
At a minimum, the requirements of NFPA 72 shall 
be followed. Environments with large amounts of 
dust, dirt or high air velocity require more 
frequent maintenance. A maintenance agreement 
must be arranged through the local 
manufacturer's representative. Maintenance must 
be scheduled monthly or as required by National 
and/or local fire codes and must be performed 
only by authorized professional fire alarm 
installers only. Adequate written records of all 
inspections must be kept. 
Installation Precautions
Adherence to the following helps in problem-free installation with long-term reliability.
WARNING - Several different sources of 
power can be connected to the fire alarm 
control panel. Disconnect all sources of power 
before servicing. Control unit and associated 
equipment may be damaged by removing and/or 
inserting cards, modules, or interconnecting 
cables while the unit is energized. Do not attempt 
to install, service, or operate this unit, until 
manuals are read and understood. 
CAUTION - System Reacceptance Test after 
Software Changes: To ensure proper system 
operation, this product must be tested in 
accordance with NFPA 72 after any programming 
operation or change in site-specific software. 
Reacceptance testing is required after any 
change, addition or deletion of system 
components, or after any modification, repair or 
adjustment to system hardware or wiring. All 
components, circuits, system operations, or 
software functions known to be affected by a 
change must be 100% tested. In addition, to 
ensure that other operations are not inadvertently 
affected, at least 10% of initiating devices that 
are not directly affected by the change, up to a 
maximum of 50 devices, must also be tested and 
proper system operation verified. 
This system meets NFPA requirements for 
operation at 0-49ºC/32-120º F and at a relative 
humidity 93% ± 2% RH (non-condensing) at 32°C 
± 2°C (90°F ± 3°F). However, the useful life of the 
system's standby batteries and the electronic 
components may be adversely affected by 
extreme temperature ranges and humidity. 
Therefore, it is recommended that this system 
and its peripherals be installed in an environment 
with a normal room temperature of 15-27º C/60-
80º F. 
Verify that wire sizes are adequate for all 
initiating and indicating device loops. Most 
devices cannot tolerate more than a 10% I.R. 
drop from the specified device voltage. 
Like all solid state electronic devices, this 
system may operate erratically or can be 
damaged when subjected to the lightning induced 
transients. Although no system is completely 
immune from lightning transients and 
interference, proper grounding reduces 
susceptibility. Overhead or outside aerial wiring is 
not recommended, due to an increased 
susceptibility to nearby lightning strikes. Consult 
with the Technical Services Department if any 
problems are anticipated or encountered. 
Disconnect AC power and batteries prior to 
removing or inserting circuit boards. Failure to do 
so can damage circuits. 
Remove all electronic assemblies prior to any 
drilling, filing, reaming, or punching of the 
enclosure. When possible, make all cable entries 
from the sides or rear. Before making 
modifications, verify that they do not interfere with 
battery, transformer, or printed circuit board 
location. 
Do not tighten screw terminals more than 9 in-
lbs. Over tightening may damage threads, 
resulting in reduced terminal contact pressure 
and difficulty with screw terminal removal. 
This system contains static-sensitive 
components. Always ground yourself with a 
proper wrist strap before handling any circuits so 
that static charges are removed from the body. 
Use static suppressive packaging to protect 
electronic assemblies removed from the unit. 
Follow the instructions in the installation, 
operating, and programming manuals. These 
instructions must be followed to avoid damage to 
the control panel and associated equipment. 
FACP operation and reliability depend upon 
proper installation.  
