Configuring ann bus, Daylight savings, Banner display – Fire-Lite PS-Tools MS-9050 User Manual
Page 43
PS-Tools User Guide
50 Pt Addr Panel
PS-Tools
08/2010
35
Daylight Savings
To configure the Daylight Savings feature
1.
Under Daylight Savings, specify the starting day and month in the Daylight Savings Time
Starts list.
2.
Specify the last day and month in the Daylight Savings Time Ends list. (see
Banner Display
To configure the banner settings
1.
Under Banner Display, click User to use a custom display. You can Type the banner display
text in Banner Text 1 and Banner Text 2.
2.
Click Factory option to display the default banner text when the fire panel is in normal mode of
operation. (see
3.
Click Save to Database to save the configuration in the PS-Tools database.
Configuring ANN Bus
ANN-Bus is a communication terminal in the fire panel over which different ANN devices can be
installed to communicate with FACP. ANN devices such as ANN-S/PG Printer Interface module,
ANN-I/O LED Driver Module, ANN-LED Annunciator Module, ANN-RLY Relay module, and
other types can be installed in the fire alarm system. You can configure the ANN-Bus, when any ANN
devices are installed.
To configure the ANN Bus
1.
Click Next at the lower-right corner of the General System Settings pane to view the ANN
Bus pane or click ANN Bus Settings > Global Options in the left pane. (see
2.
Click Yes for ANN Bus Enable, to enable the ANN Bus. You must enable the ANN Bus, if
ANN devices are installed on the ANN Bus terminals.
3.
In ANN Bus Address, select the Module Type for each address.